Chapter 8 Specifications | IED-S
8-4
8-4 Operation, Storage and Transportation Environments
DO NOT expose the drive to a poor environment, such as one with dust, direct sunlight, corrosive or inflammable
gases, oil, humidity, liquids or excessive vibration. The salt in the air must be less than 0.01 mg/cm
2
every year.
Environment
Installation
Location
IEC60364-1/IEC60664-1 pollution degree 2. Indoor use only.
Surrounding
Temperature
Operation
-10–40°C, up to 50°C with derating for the operating temperature
40–50°C
with
Derating
5.5–30 kW: for every 1°C increase in temperature,
decrease the drive’s rated current by 2.5%
37–75 kW: for every 1°C increase in temperature,
decrease the drive’s rated current by 2.0%
Storage /
Transportation
-20–60°C
Non-condensing, non-freezing
Rated
Humidity
Operation
Max. 90%
Storage /
Transportation
Max. 90%
Non-condensing, non-freezing
Altitude Operation
If the drive is installed at an altitude of 0–1000 m, follow normal
operation restrictions. For altitudes of 1000–3000 m, decrease the
drive’s rated current by 1% or lower the temperature by 0.5°C for every
100 m increase in altitude. The maximum altitude for corner grounding
is 3000 m. If installing at an altitude higher than 3000 m is required,
contact Delta for more information.
Power
System
TN system
*1*2
Package
Drop
Storage
ISTA procedure 1A (according to weight) IEC60068-2-31
Transportation
Vibration
1.0 mm, peak-to-peak value range from 2–13.2 Hz
0.7–1.0 G, range from 13.2–55 Hz
Compliance with IEC 60068-2-6
Impact
Compliance with IEC/EN 60068-2-27
Protection
Level
IP00
EMC Level IEC 61800-3 and IEC 61000-4
*1: TN system: The neutral point of the power system connects directly to the ground. The exposed metal components connect to
the ground through the protective grounding conductor.
*2: Single-phase models use a single-phase three-wire power system.
Содержание IED-S Series
Страница 3: ......
Страница 10: ...Chapter 1 Introduction IED S 1 3 1 2 Model Name 1 3 Serial Number...
Страница 24: ...Chapter 2 Installation IED S 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 25: ...Chapter 2 Installation IED S 2 6 The page intentionally left blank...
Страница 29: ...Chapter 3 Wiring IED S 3 4 IED S Integrated Elevator Drive System Wiring Diagram 01 System Configuration...
Страница 32: ...Chapter 3 Wiring IED S 3 7...
Страница 35: ...Chapter 3 Wiring IED S 3 10 3 3 Related Wiring Diagrams 03 Main Circuit for Drive Control Synchronous...
Страница 36: ...Chapter 3 Wiring IED S 3 11 04 Main Circuit for Drive Control Asynchronous...
Страница 38: ...Chapter 3 Wiring IED S 3 13 06 Safety Hatch...
Страница 39: ...Chapter 3 Wiring IED S 3 14 07 Brake Circuit...
Страница 40: ...Chapter 3 Wiring IED S 3 15 08 Inspection Circuit Cartop Inspection Connected to IED S Control Board...
Страница 42: ...Chapter 3 Wiring IED S 3 17 10 Input Contacts of Main Control Board for the Control Panel...
Страница 43: ...Chapter 3 Wiring IED S 3 18 11 Output Contacts of Main Control Board for the Control Panel...
Страница 44: ...Chapter 3 Wiring IED S 3 19 12 Contacts of Cartop Board OCB...
Страница 45: ...Chapter 3 Wiring IED S 3 20 13 Maneuvering Box 1 16 Floor ICB...
Страница 46: ...Chapter 3 Wiring IED S 3 21 14 1 Hall Call System...
Страница 50: ...Chapter 3 Wiring IED S 3 25 15 Lighting Circuit...
Страница 51: ...Chapter 3 Wiring IED S 3 26 16 UCMP Board Three Sensors DZU FL1 and DZD...
Страница 52: ...Chapter 3 Wiring IED S 3 27 17 UCMP Board Four Sensors DZU FL1 FL2 and DZD...
Страница 66: ...Chapter 5 Control Terminals IED S 5 1 Chapter 5 Control Terminals 5 1 Control Terminal Specifications...
Страница 67: ...Chapter 5 Control Terminals IED S 5 2 5 1 Control Terminal Specifications...
Страница 73: ...Chapter 5 Control Terminals IED S 5 8 The page intentionally left blank...
Страница 115: ...Chapter 6 Optional Accessories IED S 6 42 EMC Filter Model No B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 116: ...Chapter 6 Optional Accessories IED S 6 43 EMC Filter Model No B84143D0150R127 Unit mm inch...
Страница 117: ...Chapter 6 Optional Accessories IED S 6 44 EMC Filter Model No B84143D0200R127 Unit mm inch...
Страница 118: ...Chapter 6 Optional Accessories IED S 6 45 EMC Filter Model No B84142A0042R122 Unit mm inch...
Страница 123: ...Chapter 6 Optional Accessories IED S 6 50 The page intentionally left blank...
Страница 143: ...Chapter 7 Option Cards IED S 7 20 The page intentionally left blank...
Страница 151: ...Chapter 9 Digital Keypad IED S 9 4 Keypad Operation Process...
Страница 176: ...Chapter 10 Auto tuning Process IED S 10 9 10 3 2 Default Settings for Output Contacts of IED S Main Control Board...
Страница 177: ...Chapter 10 Auto tuning Process IED S 10 10 10 3 3 Default Settings for Contacts of IED S Cartop Board...
Страница 201: ...Chapter 10 Auto tuning Process IED S 10 34 The page intentionally left blank...
Страница 249: ...Chapter 11 Summary of Parameter Settings IED S 11 48 The page intentionally left blank...
Страница 263: ...Chapter 12 Descriptions of Parameter Settings IED S 12 00 14 The page intentionally left blank...
Страница 273: ...Chapter 12 Descriptions of Parameter Settings IED S 12 01 10 The page intentionally left blank...
Страница 281: ...Chapter 12 Descriptions of Parameter Settings IED S 12 02 8 The page intentionally left blank...
Страница 307: ...Chapter 12 Descriptions of Parameter Settings IED S 12 05 6 The page intentionally left blank...
Страница 319: ...Chapter 12 Descriptions of Parameter Settings IED S 12 06 12 The page intentionally left blank...
Страница 325: ...Chapter 12 Descriptions of Parameter Settings IED S 12 07 6 The page intentionally left blank...
Страница 345: ...Chapter 12 Descriptions of Parameter Settings IED S 12 10 8 The page intentionally left blank...
Страница 349: ...Chapter 12 Descriptions of Parameter Settings IED S 12 11 4 The page intentionally left blank...
Страница 359: ...Chapter 12 Descriptions of Parameter Settings IED S 12 12 10 The page intentionally left blank...
Страница 375: ...Chapter 12 Descriptions of Parameter Settings IED S 12 13 16 The page intentionally left blank...
Страница 381: ...Chapter 13 Warning Codes IED S 13 6 The page intentionally left blank...
Страница 415: ...Appendix A Single phase Application IED S A 4 The page intentionally left blank...
Страница 417: ...Appendix B Revision History IED S B 2 The page intentionally left blank...