AH500 Hardware Manual
Error
Description
Remedy
code
16#200D
An error occurs when the
binary number is converted
into the binary-coded decimal
number. (SM0/SM5)
Check the program, compile the program again,
and download the program again.
16#200E
The string does not end with
0x00. (SM0/SM5)
Check the program, compile the program again,
and download the program again.
16#200F
The instruction does not
support the modification by an
index register. (SM5)
Check the program, compile the program again,
and download the program again.
16#2010
1. The instruction does not
support the device.
2. Encoding error
3. The instruction is a 16-bit
instruction, but the constant
operand is a 32-bit code.
(SM5)
Check the program, compile the program again,
and download the program again.
16#2011
The number of operands is
incorrect. (SM5)
Check the program, compile the program again,
and download the program again.
16#2012
Incorrect division operation
(SM0/SM5).
Check the program, compile the program again,
and download the program again.
16#2013
The value exceeds the range
of values which can be
represented by the
floating-point numbers.
(SM0/SM5)
Check the program, compile the program again,
and download the program again.
16#2014
The task designated by
TKON/YKOFF is incorrect, or
exceeds the range. (SM5)
Check the program, compile the program again,
and download the program again.
16#2015
There are more than 32 levels
of nested program structures
supported by CALL. (SM0)
Check the program, compile the program again,
and download the program again.
16#2016
There are more than 32 levels
of nested program structures
supported by FOR/NEXT.
(SM0/SM5)
Check the program, compile the program again,
and download the program again.
16#2017
The number of times FOR is
used is different from the
number of times NEXT is
used. (SM5)
Check the program, compile the program again,
and download the program again.
16#2018
There is a label after FEND,
but there is no SRET.
There is SRET, but there is no
label. (SM5)
1. Compile the program again, and download the
program again.
2. Reinstall ISPSoft, compile the program again,
and download the program again.
16#2019
The interrupt task is not after
FEND. (SM5)
1. Compile the program again, and download the
program again.
2. Reinstall ISPSoft, compile the program again,
and download the program again.
16#201A
IRET/SRET is not after FEND.
(SM5)
1. Compile the program again, and download the
program again.
2. Reinstall ISPSoft, compile the program again,
and download the program again.
9-6
Содержание AH02HC-5A
Страница 1: ......
Страница 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Страница 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Страница 125: ...Chapter 5 OOWiring 5 4 3 Wiring AH16AN01T 5A Input type Transistor T sinking Voltage specifications 12 30 V DC 5 12...
Страница 126: ...AH500 Hardware Manual 5 4 4 Wiring AH16AN01P 5A Input type Transistor P sourcing Voltage specifications 12 30 V DC 5 13...
Страница 127: ...Chapter 5 OOWiring 5 4 5 Wiring AH16AN01R 5A Input type Relay R Voltage specifications Below 250 V AC below 30 V DC 5 14...
Страница 128: ...AH500 Hardware Manual 5 4 6 Wiring AH16AN01S 5A Input type TRIAC S Voltage specifications 120 240 V AC 5 15...
Страница 181: ...Chapter 5 OOWiring 5 68 MEMO...
Страница 189: ...AH500 Hardware Manual MEMO 7 4...
Страница 195: ...AH500 Hardware Manual MEMO 8 6...
Страница 229: ...AH500 Hardware Manual MEMO 9 34...