AH500 Hardware Manual
Error
Description
Remedy
code
16#A801
The signal received by
channel 1 exceeds the range
of inputs which can be
received by the hardware.
(The ERROR LED indicator is
OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 1
exceeds the range of inputs which can be received
by the hardware.
16#A802
The signal received by
channel 2 exceeds the range
of inputs which can be
received by the hardware.
(The ERROR LED indicator is
OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 2
exceeds the range of inputs which can be received
by the hardware.
16#A803
The signal received by
channel 3 exceeds the range
of inputs which can be
received by the hardware.
(The ERROR LED indicator is
OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 3
exceeds the range of inputs which can be received
by the hardware.
16#A804
The signal received by
channel 4 exceeds the range
of inputs which can be
received by the hardware.
(The ERROR LED indicator is
OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 4
exceeds the range of inputs which can be received
by the hardware.
16#A805
The signal received by
channel 5 exceeds the range
of inputs which can be
received by the hardware.
(The ERROR LED indicator is
OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 5
exceeds the range of inputs which can be received
by the hardware.
16#A806
The signal received by
channel 6 exceeds the range
of inputs which can be
received by the hardware.
(The ERROR LED indicator is
OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 6
exceeds the range of inputs which can be received
by the hardware.
16#A807
The signal received by
channel 7 exceeds the range
of inputs which can be
received by the hardware.
(The ERROR LED indicator is
OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 7
exceeds the range of inputs which can be received
by the hardware.
9.2.2
Troubleshooting for AH02HC-5A/AH04HC-5A
Error
code
Description
Remedy
16#A001
The linear accumulation in
channel 1 exceeds the range.
To clear the linear accumulation, users need to set
bit 1 in CR0 to ON by means of FROM/TO.
16#A002
The prescale value for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The prescale value for channel 1 should be within
the range between 0 and 32767.
16#A003
The moving average for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The moving average for channel 1 should be within
the range between 2 and 60.
9-26
Содержание AH02HC-5A
Страница 1: ......
Страница 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Страница 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Страница 125: ...Chapter 5 OOWiring 5 4 3 Wiring AH16AN01T 5A Input type Transistor T sinking Voltage specifications 12 30 V DC 5 12...
Страница 126: ...AH500 Hardware Manual 5 4 4 Wiring AH16AN01P 5A Input type Transistor P sourcing Voltage specifications 12 30 V DC 5 13...
Страница 127: ...Chapter 5 OOWiring 5 4 5 Wiring AH16AN01R 5A Input type Relay R Voltage specifications Below 250 V AC below 30 V DC 5 14...
Страница 128: ...AH500 Hardware Manual 5 4 6 Wiring AH16AN01S 5A Input type TRIAC S Voltage specifications 120 240 V AC 5 15...
Страница 181: ...Chapter 5 OOWiring 5 68 MEMO...
Страница 189: ...AH500 Hardware Manual MEMO 7 4...
Страница 195: ...AH500 Hardware Manual MEMO 8 6...
Страница 229: ...AH500 Hardware Manual MEMO 9 34...