Chapter 9 Troubleshooting
Error
Description
Remedy
code
16#6606
There is a routing response
timeout.
1. Check the network configuration in NWCONFIG.
2. Check whether the setting of the communication
timeout conform to the practical application.
16#8105
The contents of the program
downloaded are incorrect.
The program syntax is
incorrect.
1. Check whether the program syntax which is not
supported by the CPU module is used, and
check whether the version of the firmware has
its special limitation.
2. Check whether the version of ISPSoft used to
create the program is the same as the version of
ISPSoft used now.
16#8106
The contents of the program
downloaded are incorrect.
The length of the execution
code exceeds the limit.
1. Shorten the length of the program, and
download the program again.
2. Check whether the version of ISPSoft used to
create the program is the same as the version of
ISPSoft used now.
16#8107
The contents of the program
downloaded are incorrect.
The length of the source code
exceeds the limit.
1. Shorten the length of the program, and
download the program again.
2. Check whether the version of ISPSoft used to
create the program is the same as the version of
ISPSoft used now.
16#820E
The communication port
parameter downloaded is
incorrect.
The communication protocol is
incorrect.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#820F
The communication port
parameter downloaded is
incorrect.
The setting of the station
address is incorrect.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8210
The communication port
parameter downloaded is
incorrect.
The choice among RS-232,
RS-485, and SR-422 is
incorrect.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8211
The communication port
parameter downloaded is
incorrect.
The interval of retrying the
sending of the command is set
incorrectly.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8212
The communication port
parameter downloaded is
incorrect.
The number of times the
sending of the command is
retried is set incorrectly.
1. Check the setting of the communication port
parameter for the CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8215
The CPU parameter
downloaded is incorrect.
The interval of executing
interrupt 0 is set incorrectly.
1. Check the setting of the basic parameter for the
CPU module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
9-15
Содержание AH02HC-5A
Страница 1: ......
Страница 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Страница 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Страница 125: ...Chapter 5 OOWiring 5 4 3 Wiring AH16AN01T 5A Input type Transistor T sinking Voltage specifications 12 30 V DC 5 12...
Страница 126: ...AH500 Hardware Manual 5 4 4 Wiring AH16AN01P 5A Input type Transistor P sourcing Voltage specifications 12 30 V DC 5 13...
Страница 127: ...Chapter 5 OOWiring 5 4 5 Wiring AH16AN01R 5A Input type Relay R Voltage specifications Below 250 V AC below 30 V DC 5 14...
Страница 128: ...AH500 Hardware Manual 5 4 6 Wiring AH16AN01S 5A Input type TRIAC S Voltage specifications 120 240 V AC 5 15...
Страница 181: ...Chapter 5 OOWiring 5 68 MEMO...
Страница 189: ...AH500 Hardware Manual MEMO 7 4...
Страница 195: ...AH500 Hardware Manual MEMO 8 6...
Страница 229: ...AH500 Hardware Manual MEMO 9 34...