C h a p t e r 4 A d d r e s s i n g
z
AH16AN01R-5A: There are 16 inputs. The
input device range
occupies 16 bits. (Y
n
.0~Y
n
.15)
z
AH16AP11R-5A: There are 8 inputs, and 8 outputs. The
input device range
occupies 16 bits,
and the
output device range
occupies 16 bits. (X
n
.0~X
n
.15, and
Y
n
.0~Y
n
.15)
z
AH32AM10N-5B: There are 32 inputs. The
input device range
occupies 32 bits.
(X
n
.0~X
n+1
.15)
z
AH32AN02T-5B: There are 32 outputs. The
output device range
occupies 32 bits.
(Y
n
.0~Y
n+1
.15)
z
AH64AM10N-5C: There are 64 inputs. The
input device range
occupies 64 bits.
(X
n
.0~X
n+3
.15)
z
AH64AN02P-5C: There are 64 inputs. The
output device range
occupies 64 bits.
(Y
n
.0~Y
n+3
.15)
4.2.2
Start Addresses for Analog Input/Output Modules
Input/Output data registers are automatically assigned to an analog input/output module through
HWCONFIG in ISPSoft according to the number of registers which is defined for the analog
input/output module. A channel occupies two words.
z
AH04AD-5A: There are 4 input channels. The
input device range
occupies 8 data registers.
z
AH08AD-5B: There are 8 input channels. The
input device range
occupies 16 data registers
z
AH06XA-5A: There are 4 input channels, and 2 output channels. The
input device range
occupies 8 data registers, and the
output device range
occupies 4 data registers.
z
AH04DA-5A:
There
are
4 output channels. The
output device range
occupies 8 data registers.
z
AH08DA-5B: There are 8 output channels. The
output device range
occupies 16 data
registers.
4 - 3
Содержание AH02HC-5A
Страница 1: ......
Страница 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Страница 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Страница 125: ...Chapter 5 OOWiring 5 4 3 Wiring AH16AN01T 5A Input type Transistor T sinking Voltage specifications 12 30 V DC 5 12...
Страница 126: ...AH500 Hardware Manual 5 4 4 Wiring AH16AN01P 5A Input type Transistor P sourcing Voltage specifications 12 30 V DC 5 13...
Страница 127: ...Chapter 5 OOWiring 5 4 5 Wiring AH16AN01R 5A Input type Relay R Voltage specifications Below 250 V AC below 30 V DC 5 14...
Страница 128: ...AH500 Hardware Manual 5 4 6 Wiring AH16AN01S 5A Input type TRIAC S Voltage specifications 120 240 V AC 5 15...
Страница 181: ...Chapter 5 OOWiring 5 68 MEMO...
Страница 189: ...AH500 Hardware Manual MEMO 7 4...
Страница 195: ...AH500 Hardware Manual MEMO 8 6...
Страница 229: ...AH500 Hardware Manual MEMO 9 34...