Ground
The diameter of the ground should not
be less than the diameters of the cables
connected to the terminals L and N.
If much equipment is used, please use
single-point ground.
AHPS05-5A Other equipment
The single-point ground is better.
If single-point ground can not be used,
please use common-point ground.
AHPS05-5A Other equipment
The common-point ground is permitted.
Users can not ground equipment in the
way shown on the right.
AHPS05-5A
Other equipment
The equipment can not be grounded in this way.
5.2.3
Wiring the Power Supply Module
Functional ground *2
Power cable *3
VS+
VS-
NC
FG
LG
L
N
PS05
CPU530
06XA
UP
ZP
P/S
24V
0V
*1
100~240V
Control box
*1. The 24 V power supply is connected to VS+ and VS- on the power supply module. VS+ and VS-
can be used to detect whether the voltage of the external power supply is stable.
*2. FG on the power supply module is connected to the control box as the functional ground.
*3. The live cable and the neutral cable are connected to L and N on the power supply module
respectively. To prevent the system from becoming abnormal, the ground has to be connected to
LG on the power supply module.
The power input of AHPS05-5A is the AC input. Users have to pay attention to the following points
when they use AHPS05-5A.
The alternating-current input voltage is within the range between 100 V AC and 240 V AC.
Please connect the power supply to the terminals L and N. If the 110 V AC or the 220 V AC
power supply is connected to the input terminals VS+ and VS-, the PLC will be damaged.
In order to ensure that the 24 V DC external power supply is provided stably, it can be
connected to VS+ and VS-. If the PLC detects that the voltage of the external power supply is
lower than the working voltage, users can write a protective program.
5-5
Содержание AH02HC-5A
Страница 1: ......
Страница 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Страница 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Страница 125: ...Chapter 5 OOWiring 5 4 3 Wiring AH16AN01T 5A Input type Transistor T sinking Voltage specifications 12 30 V DC 5 12...
Страница 126: ...AH500 Hardware Manual 5 4 4 Wiring AH16AN01P 5A Input type Transistor P sourcing Voltage specifications 12 30 V DC 5 13...
Страница 127: ...Chapter 5 OOWiring 5 4 5 Wiring AH16AN01R 5A Input type Relay R Voltage specifications Below 250 V AC below 30 V DC 5 14...
Страница 128: ...AH500 Hardware Manual 5 4 6 Wiring AH16AN01S 5A Input type TRIAC S Voltage specifications 120 240 V AC 5 15...
Страница 181: ...Chapter 5 OOWiring 5 68 MEMO...
Страница 189: ...AH500 Hardware Manual MEMO 7 4...
Страница 195: ...AH500 Hardware Manual MEMO 8 6...
Страница 229: ...AH500 Hardware Manual MEMO 9 34...