Chapter 5
OOWiring
Grounding a cable
Please ground a cable according to the steps below.
(1) Please ground a cable correctly.
(2) The area of the cross-section of the cable which is grounded should be 2 mm
2
or larger
than 2 mm
2
.
(3) The ground point should be near the PLC. Ground the cable properly.
Note
(1) The 110 V/220 V power cable and the 24 V DC power cable should be thick cables. (The area of
the cross-section of the cable is 2 mm
2
, and the diameter of the cable is 14 AWG.) Be sure to
twist the power cables at terminal screws. To prevent the short circuit which results from loose
screws, users need to use solderless terminals with insulation sleeves.
(2) If cables are connected to the terminals LG and FG, the cables need to be grounded. Do not
connect LG and FG to any devices. If LG and FG are not grounded, the PLC will be susceptible
to noise. Since LG have potential, users will get an electric shock if they touch metal parts.
5.2
Power Wiring
5.2.1
Precautions
The power wiring
(a) Please separate the power cable of AHPS05-5A from the power cables for the I/O device
and the power device. If there is much noise, connect an isolating transformer.
AC power supply
100-240 V
AHPS05-5A
I/O equipment
Other equipment
Isolating transformer
(b) The 110 V AC cable, the 220 V AC cable, and the 24 V DC cable should be twisted, and
connected to a module within a short distance.
(c) Do not bundle 110 V AC cable, the 220 V AC cable, the 24 V DC cable, the main circuit, and
the I/O signal cable together. Besides, it is recommended that the distance between
adjacent cables is 100 millimeters.
(d) To prevent the surge resulting from lightning, please install a surge absorber as follows.
AC power supply
100-240V
AHPS05-5A
I/O equipment
Surge absorber
Note:
1. The surge absorber and the PLC system should be grounded at different places.
2. Please select the surge absorber whose working voltage is not less than the maximum
allowable input voltage.
5-4
Содержание AH02HC-5A
Страница 1: ......
Страница 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Страница 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Страница 125: ...Chapter 5 OOWiring 5 4 3 Wiring AH16AN01T 5A Input type Transistor T sinking Voltage specifications 12 30 V DC 5 12...
Страница 126: ...AH500 Hardware Manual 5 4 4 Wiring AH16AN01P 5A Input type Transistor P sourcing Voltage specifications 12 30 V DC 5 13...
Страница 127: ...Chapter 5 OOWiring 5 4 5 Wiring AH16AN01R 5A Input type Relay R Voltage specifications Below 250 V AC below 30 V DC 5 14...
Страница 128: ...AH500 Hardware Manual 5 4 6 Wiring AH16AN01S 5A Input type TRIAC S Voltage specifications 120 240 V AC 5 15...
Страница 181: ...Chapter 5 OOWiring 5 68 MEMO...
Страница 189: ...AH500 Hardware Manual MEMO 7 4...
Страница 195: ...AH500 Hardware Manual MEMO 8 6...
Страница 229: ...AH500 Hardware Manual MEMO 9 34...