8. Phase connection pattern
DEFA recommends phase rotation in the distributed circuits, one step per charge point,
as shown in the example installation diagrams. By using a connection pattern with phase
rotation, the system ensures an even load distribution among the phases.
Phase rotation is important for single-phase charging, and for three-phase charging when
single-phase vehicles are connected. PE-wiring is intentionally not shown in the installation
diagrams.
SUPPLY FROM 400V / 3-PHASE / TN NETWORK WITH NEUTRAL
Site current
per phase [A]
Site current per phase with
5% margin of safety [A]
Maximum number of
charging vehicles per phase
Maximum number of
charging vehicles in total
32
30
5
15
35
33
5
15
40
38
6
18
50
47
7
21
63
59
9
27
80
76
12
36
100
95
15
45
125
118
19
57
150
142
23
69
180
171
28
84
200
190
31
93
250
237
39
117
300
285
47
141
350
332
55
165
400
380
63
189
IT NETWORK, PHASE ROTATION, SINGLE PHASE
CHARGING
TN NETWORK, PHASE ROTATION, SINGLE PHASE
CHARGING