8. Troubleshooting
8.1 Error codes
The boiler is fitted with an electronic regulation and
control unit. The heart of the control system is a
microprocessor, the
Comfort Master
©
, which controls
the boiler and also protects the boiler. If a fault is
detected anywhere in the boiler, the boiler locks out
and the display will show the fault code as follows:
In a red flashing display:
• The symbol
• The symbol
RESET
• The fault code (for example
E
:
01
)
The meaning of the error codes is given in the error
table. To do this, proceed as follows:
Error
code
Description
Probable causes
Checking / solution
é
:
00
Storage unit PSU
parameter not found
• Bad connection
• Check the wiring
é
:
01
The safety parameters
are incorrect
• Bad connection
• PSU defective
• Check the wiring
• Replace PSU
é
:
02
Supply temperature
sensor short circuited
• Bad connection
• Sensor fault
• Sensor not or badly connected
• Check the wiring
• Check that the sensors are operating correctly
• Check that the sensor has been correctly fitted
• Replace the sensor if necessary
é
:
03
Supply temperature
sensor open circuit
• Bad connection
• Sensor fault
• Sensor not or badly connected
• Check the wiring
• Check that the sensors are operating correctly
• Check that the sensor has been correctly fitted
• Replace the sensor if necessary
é
:
04
é
:
05
Temperature of heat
exchanger too low
Exchanger temperature
too high
• Bad connection
• Sensor fault
• Sensor not or badly connected
• No circulation
• Check the wiring
• Replace the sensor if necessary
• Vent the air in the heating system
• Check the circulation (direction, pump, valves)
• Check the water pressure
• Check that the sensors are operating correctly
• Check that the sensor has been correctly fitted
• Check the cleanliness of the heat exchanger
i
Note the error code displayed.
The fault code is important for correct and
fast tracing of the nature of the fault and for
obtaining support from your heating contractor.
• Press the
RESET
button for 2 seconds. If the error
code continues to display, search for the cause in
the error table and apply the solution.
i
If the display does not show
RESET
but rather
, the boiler must be switched OFF and then
switched ON again after 10 seconds before the
fault can be reset.