MCA
Pro
45/65/90/115
MCA-Pro ISM Rv.4.1 2/2017
100
Shutdown
code
Description
Probable causes
Checking / solution
5
:
0
Parameter error
• Parameter error on the PSU PCB
• Reset
df
and
dU
• Restore parameters with Recom
5
:
1
Maximum supply
temperature
exceeded
•
Non-existent or insufficient
circulation
• Check the circulation (direction, pump,
valves)
• Reasons for the heat demand
5
:
2
Maximum increase
of the
flow temperature
has been
exceeded
•
Non-existent or insufficient
circulation
• Sensor error
• Check the circulation (direction, pump,valves)
• Check the water pressure
• Check that the sensors are operating correctly
•
Check that the sensor has been correctly fitted
• Check the cleanliness of the heat exchanger
5
:
7
No release signal
• External cause
• Parameter error
• Bad connection
• Suppress the external cause
• Check the parameters
• Check the wiring
5
:
9
Phase and neutral of
mains supply mixed
up
• Mains supply incorrectly wired
• Floating or 2 phase network
• Phase and neutral mixed up
• Set parameter
p43
to
0
5
:
10
Shutdown input is
open
• External cause
• Parameter error
• Bad connection
• Suppress the external cause
• Check the parameters
• Check the wiring
5
:
11
Shutdown input
active or frost
protection active
• External cause
• Parameter error
• Bad connection
• Suppress the external cause
• Check the parameters
• Check the wiring
5
:
13
Communication
error with the
SCU PCB
• Bad connection with BUS
• SCU PCB not installed in the
boiler
• Check the wiring
• Carry out automatic detection
5
:
14
Water pressure too
low
• Water pressure too low
• Check the water pressure
• Fill the boiler and the installation with water
5
:
15
Gas pressure too
low
•
Non-existent or insufficient
circulation
• Incorrect setting of the Gps gas
pressure switch on the SCU PCB
• Check that the gas valve is fully opened
• Check the supply pressure
• Check whether the Gps gas pressure control
system has been correctly fitted
• Replace the Gps gas pressure control system if
need be
5
:
16
(1)
Configuration fault
or SU PCB not
recognised
• Wrong SU PCB for this boiler
• Replace the SU PCB
5
:
17
(1)
Configuration fault
or default parameter
table incorrect
• Parameter error on the PCU PCB
• Replace the PCU PCB
8. Troubleshooting