73
MCA
Pro
45/65/90/115
MCA-Pro ISM Rv.4.1 2/2017
5.6.3. Status and sub-status
The information menu
gives the following status and sub-status numbers:
5. Commissioning
State
5t
Sub-status
5
0
Rest
0
Rest
1
Boiler start (Heat demand)
1
Short cycling protection function
2
Control three-way valve
3
Start pump
4
Wait for the correct temperatures for burner start
2
Burner start
10
Open flue gas damper/external gas valve
11
Increase fan speed
13
Pre-purge
14
Wait for release signal
15
Burner on
17
Pre-ignition
18
Main ignition
19
Flame detection
20
Intermediate ventilation
3
Burning for heating system operation
30
Temperature control
31
Limited temperature control (ΔT safety)
32
Output control
33
Temperature protection gradient level 1 (Modulate
down)
34
Temperature protection gradient level 2 (Part load)
35
Temperature protection gradient level 3 (Blockage)
36
Modulate up for flame control
37
Temperature stabilisation time
38
Cold start
4
DHW mode running
30
Temperature control
31
Limited temperature control (ΔT safety)
32
Output control
33
Temperature protection gradient level 1 (Modulate
down)
34
Temperature protection gradient level 2 (Part load)
35
Temperature protection gradient level 3 (Blockage)
36
Modulate up for flame control
37
Temperature stabilisation time
38
Cold start
5
Burner stop
40
Burner off
41
Post-purge
42
Close flue gas damper/external gas valve
43
Recirculation protection
44
Stop fan