5.4.3. Setting the air/gas ratio (Part load)
1. Unscrew the plug of the flue gas measurement
point.
2. Connect the flue gas analyser.
WARNING
Ensure that the opening around the combustion
analyzer probe is completely sealed when taking
measurements.
3. Set the boiler to part load. Press the [-] key several
times until
l3
is displayed on the screen.
4. Measure the percentage of O
2
or CO
2
in the flue
gases.
5. Compare the values measured with the checking
values given in the table (Front panel removed).
6. If necessary, adjust the gas/air ratio using the
adjusting screw
(B)
.
Control and setting values O
2
/CO
2
at part load for natural gas
Boiler type
Setting value
Checking value
O
2
(%)
CO
2
(%)
O
2
(%)
CO
2
(%)
MCA Pro 45
5.6/5.9
8.4/8.6
5.4/6.1
8.3/8.7
MCA Pro 65
5.6/5.9
8.4/8.6
5.4/6.1
8.3/8.7
MCA Pro 90
5.6/5.9
8.4-8.6
5.4/6.1
8.3/8.7
MCA Pro 115
5.4/5.7
8.5/8.7
5.2/5.9
8.4/8.8
Control and setting values O
2
/CO
2
at part load for propane
Boiler type
Setting value
Checking value
O
2
(%)
CO
2
(%)
O
2
(%)
CO
2
(%)
MCA Pro 45
5.2/5.5
10.1/10.3
5.1/5.7
10.0/10.4
MCA Pro 65
5.2/5.5
10.1/10.3
5.1/5.7
10.0/10.4
MCA Pro 90
Propane not available
MCA Pro 115
6.3/6.6
9.4/9.6
6.1/6.7
9.3/9.7