MCA-Pro ISM Rv.4.1 2/2017
Shutdown
code
Description
Probable causes
Checking / solution
5
:
18
Configuration fault
or PCU PCB not
recognised
Wrong PCU PCB for this
boiler
• Replace the PCU PCB
5
:
19
Configuration fault
or parameters
df
-
d
unknown
• Reset
df
and
d
5
:
20
Configuration
procedure
active
• Active for a short time after
switching on the boiler
• No action required
5
:
21
Communication
error with the
SU PCB
• Bad connection
• Check whether the PCU PCB has been
correctly fitted in the connector on SU PCB
5
:
22
No flame during
operation
• No ionization current
• Purge the gas supply to remove air
• Check that the gas valve is fully opened
• Check the supply pressure
• Check the operation and setting of the gas
valve unit
•
Check that the air inlet and flue gas discharge
flues are not blocked
•
Check that there is no recirculation of flue
5
:
25
(1)
Internal error on the
5U
-
PCb
SU PCB
• Replace the SU PCB
5
:
29
FG
sensor above
maximum setpoint
Non-existing or insufficient
circulation / sensor error
Replace the flue gas sensor.
5
:
30
No
TFG
sensor
connected / shorted
Boiler stop
Fluegas sensor disconnected /
Sensor error
Replace the flue gas sensor.
5
:
32
TFG1
and
TFG2
max.
deviation exceeded
Non-existing or insufficient
circulation / sensor error
Replace the fue gas sensor.
5
:
33
after 5 times
TF
>
Tf
Max:
controlled stop
Non-existing or insufficient
circulation / sensor error
Replace the flow sensor.
5
:
34
after 5 times
TFG
>
Tf
max:
controlled stop
Non-existing or insufficient
circulation / sensor error
Replace the flue gas sensor.
(1) These lock-outs are not stored in the fault memory
8. Troubleshooting