4.9.5. Connecting a third party control unit
Connecting modulating controller
OT
OpenTherm
regulator
The boiler is fitted with a
OpenTherm
connection as
standard.
As a result, modulating
OpenTherm
controllers can
be connected without further modifications (Room,
weather-dependent and cascade controllers).
• In the case of a room thermostat: Install the room
thermostat in the reference room (generally the
living room).
• Connect the two-wire cable to terminals
ON/OFF-OT
of the connector.
i
If the DHW temperature can be set on the
OpenTherm
controller, then the boiler supplies
this temperature, with the set value on the
boiler as the maximum.
Connect ON/OFF thermostat
Tk
ON/OFF room thermostat
The boiler is suitable for connection to a 2 wire ON/OFF
room thermostat.
• Install the room thermostat in the reference room
(generally the living room).
• Connect the 2 wire 24V room thermostat to the
ON/OFF-OT
terminals of the connector.
i
If a room thermostat with an anticipation
element is used, this must be converted using
parameter
p5
.
Note:
This boiler is not suitable for a Nest type
thermostat without an external AC power supply.
- Standard boiler configuration : DC 24v - 7mA
- Optional boiler configuation : DC 24v - 120mA
On/off
OT
BL
RL Tout Tdhw
OT
On/of
f
Tout
Tdhw
BL
RL
OT
Tk
OT
On/off
Tout
Tdhw
BL
RL
On/off
OT
BL
RL Tout Tdhw
4. Installation