AMT58x-CB CANopen®
26
6.8.2 Manufacturer specific objects
2104-00 Limit switch min.
[Unsigned32, rw]
This object can be used to set the lowest software limit switch. (-).
If the encoder position is below the value set in this object, bit 12 of
object
6500-00 Operating state
will be set to 1.
To enable this function set bit 12 of object
6000-00 Operating
parameters
to 1.
Default = 0000 0010h
2105-00 Limit switch max.
[Unsigned32, rw]
This object can be used to set the highest software limit switch. (+).
If the encoder position is higher than the value set in this object, bit
13 of object
6500-00 Operating state
will be set to 1.
To enable this function set bit 13 of object
6000-00 Operating
parameters
to 1.
Default = 003F FFF0h
3000-00 Baud rate
[Unsigned8, rw]
This object is meant to set the baud rate (transmission rate)
according to the following table:
Data byte
Baud rate
00h
20 Kbit/s
01h 50
Kbit/s
02h
100 Kbit/s
03h 125
Kbit/s
04h
250 Kbit/s
05h
500 Kbit/s (default)
06h
800 Kbit/s
07h 1000
Kbit/s
The bit rate is set through object
3000-00 Baud rate
only if bit 4 in
DIP A is set to ”OFF”. If bit 4 in DIP A is set to ”ON”, the bit rate is set
by DIP A. For any further information refer to section “
Errore.
L'origine riferimento non è stata trovata.
”.
To change the baud rate value you have to:
set the object
3000-00 Baud rate
;
send a Reset node command (or Reset communication
command);
save the parameter;
set the Master to the new baud rate.
Default = 05h
Содержание AMT58 Series
Страница 1: ......
Страница 8: ......
Страница 13: ...AMT58x CB CANopen 5 3 1 3 Fissaggio con flangia codice ST 58 FLNG ...
Страница 52: ......
Страница 55: ...Subject index ...
Страница 62: ...AMT58x PB Profibus 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Страница 101: ......
Страница 102: ......
Страница 109: ......
Страница 114: ...AMT58x EC EtherCAT 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Страница 166: ......
Страница 167: ...AMT58 PN INSTRUCTION MANUAL Absolute Encoders ...
Страница 179: ...INSTRUCTION MANUAL xiii SFC System function TCP Transmission Control Protocol TMAPC Master Application Cycle Time ...
Страница 180: ...LIST OF ABBREVIATIONS xiv AMT58 PN ...
Страница 213: ...RESETTING THE PARAMETERS TO THE DEFAULT FACTORY VALUES INSTRUCTION MANUAL 33 Figure 15 Encoder reset ...
Страница 221: ...TO TECHNOLOGY OBJECTS INSTRUCTION MANUAL 41 Figure 28 TO encoder enabled ...
Страница 231: ...INSTRUCTION MANUAL 51 ...
Страница 255: ...REAL TIME CLASS 3 IRT_TOP RT3 INSTRUCTION MANUAL 75 Figure 5 Telegram 81 IN Figure 6 Telegram 81 OUT ...
Страница 265: ...NORMAL OPERATION DIAGRAM INSTRUCTION MANUAL 85 NORMAL OPERATION DIAGRAM ...
Страница 266: ...ENCODER STATE MACHINE 86 AMT58 PN PRESET DIAGRAM ...
Страница 267: ...PARKING SENSOR DIAGRAM INSTRUCTION MANUAL 87 PARKING SENSOR DIAGRAM ...
Страница 268: ...ENCODER STATE MACHINE 88 AMT58 PN ERROR DIAGRAM Acknowledgment of acknowledgeable sensor error ...
Страница 269: ...ERROR DIAGRAM INSTRUCTION MANUAL 89 Acknowledgment of not acknowledgeable sensor error ...
Страница 284: ......
Страница 285: ......
Страница 287: ......
Страница 294: ......
Страница 299: ...AMT58x CB CANopen 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Страница 335: ......
Страница 345: ...AMT58x DN DeviceNET 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Страница 380: ...AMT58x DN DeviceNET 40 Default 21h ...
Страница 384: ...AMT58x DN DeviceNET 44 Default 00h ...
Страница 394: ......
Страница 404: ...AMT58x PB Profibus 5 3 1 3 Installation using a flange code ST 58 FLNG ...