3.8.11. Remote mounting Kit for LCP
The Local Control Panel can be moved to the
front of a cabinet by using the remote build in
kit. The enclosure is the IP65. The fastening
screws must be tightened with a torque of
max. 1 Nm.
Technical data
Enclosure:
IP 65 front
Max. cable length between VLT
and unit:
3 m
Communication std:
RS 485
3.8.12. IP 21/IP 4X/ TYPE 1 Enclosure Kit
IP 20/IP 4X top/ TYPE 1 is an optional enclosure element available for IP 20 Compact units, en-
closure size A2-A3.
If the enclosure kit is used, an IP 20 unit is upgraded to comply with enclosure IP 21/ 4X top/
TYPE 1.
The IP 4X top can be applied to all standard IP 20 VLT HVAC variants.
3.8.13. IP 21/Type 1 Enclosure Kit
A – Top cover
B – Brim
C – Base part
D – Base cover
E – Screw(s)
Place the top cover as shown. If an A or B
option is used the brim must be fitted to cov-
er the top inlet. Place the base part C at the
bottom of the drive and use the clamps from
the accessory bag to correctly fasten the ca-
bles. Holes for cable glands:
Size A2: 2x M25 and 3xM32
Size A3: 3xM25 and 3xM32
3. VLT HVAC Selection
VLT
®
HVAC Drive Design Guide
76
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark