7.10.4. Read Holding Registers (03 HEX)
Description
This function reads the contents of holding registers in the slave.
Query
The query message specifies the starting register and quantity of registers to be read. Register
addresses start at zero, i.e. registers 1-4 are addressed as 0-3.
Field Name
Example (HEX)
Slave Address
01
Function
03 (read holding registers)
Starting Address HI
00
Starting Address LO
00 (coil address 17)
No. of Points HI
00
No. of Points LO
03
Error Check (CRC)
-
Response
The register data in the response message are packed as two bytes per register, with the binary
contents right justified within each byte. For each register, the first byte contains the high order
bits and the second contains the low order bits.
Field Name
Example (HEX)
Slave Address
01
Function
03
Byte Count
06
Data HI
(Register 40001)
55
Data LO
(Register 40001)
AA
Data HI
(Register 40002)
55
Data LO
(Register 40002)
AA
Data HI
(Register 40003)
55
Data LO
(Register 40003)
AA
Error Check
(CRC)
-
VLT
®
HVAC Drive Design Guide
7. RS-485 Installation and Set-up
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
143
7