5.2.4. Motor Connection
NB!
Motor cable must be screened/armoured. If an unscreened/unarmoured cable is
used, some EMC requirements are not complied with. For more information, see
EMC specifications
.
1.
Fasten decoupling plate to the bot-
tom of the frequency converter with
screws and washers from the acces-
sory bag.
Illustration 5.7: Mounting of decoupling plate
2.
Attach motor cable to terminals 96
(U), 97 (V), 98 (W).
3.
Connect to earth connection (termi-
nal 99) on decoupling plate with
screws from the accessory bag.
4.
Insert terminals 96 (U), 97 (V), 98
(W) and motor cable to terminals la-
belled MOTOR.
5.
Fasten screened cable to decoupling
plate with screws and washers from
the accessory bag.
Illustration 5.8: Motor connection for enclosures
A2 and A3
Illustration 5.9: Motor connection for enclosure A5
5. How to Install
VLT
®
HVAC Drive Design Guide
88
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
5