1.
Use a clamp from the accessory bag
to connect the screen to the frequen-
cy converter decoupling plate for
control cables.
See section entitled
Earthing of Screened/
Armoured Control Cables
for the correct ter-
mination of control cables.
5.2.13. Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used
to select a current (0-20 mA) or a voltage (0
to 10 V) configuration of the analog input ter-
minals 53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable
termination on the RS-485 port (terminals 68
and 69).
See drawing
Diagram showing all electrical
terminals
in section
Electrical Installation.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF