7.4.6. The Data Field
The structure of data blocks depends on the type of telegram. There are three telegram types,
and the type applies for both control telegrams (master=>slave) and response telegrams
(slave=>master).
The three types of telegram are:
Process block (PCD):
The PCD is made up of a data block of four bytes (2 words) and contains:
- Control word and reference value (from master to slave)
- Status word and present output frequency (from slave to master).
Parameter block:
The parameter block is used to transfer parameters between master and slave. The data block is
made up of 12 bytes (6 words) and also contains the process block.
Text block:
The text block is used to read or write texts via the data block.
7.4.7. The PKE Field
The PKE field contains two sub-fields: Parameter command and response AK, and Parameter
number PNU:
7. RS-485 Installation and Set-up
VLT
®
HVAC Drive Design Guide
128
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
7