5.2.10. Electrical Installation, Control Terminals
To mount the cable to the terminal:
1.
Strip isolation of 9-10 mm
2.
Insert a screw driver
1)
in the square
hole.
3.
Insert the cable in the adjacent cir-
cular hole.
4.
Remove the screw driver. The cable
is now mounted to the terminal.
To remove the cable from the terminal:
1.
Insert a screw driver
1)
in the square
hole.
2.
Pull out the cable.
1)
Max. 0.4 x 2.5 mm
1.
2.
3.
Assembling of IP55 / NEMA TYPE 12 housing
with mains disconnector
5.2.11. Basic Wiring Example
1.
Mount terminals from the accessory
bag to the front of the frequency
converter.
2.
Connect terminals 18 and 27 to +24
V (terminal 12/13)
Default settings:
18 = latched start
27 = stop inverse
Illustration 5.15: Terminal 37 available with Safe
Stop Function only!
5. How to Install
VLT
®
HVAC Drive Design Guide
94
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
5