5.5. Installation of misc. connections
5.5.1. RS 485 Bus Connection
One or more frequency converters can be con-
nected to a control (or master) using the
RS485 standardized interface. Terminal 68 is
connected to the P signal (TX+, RX+), while
terminal 69 is connected to the N signal
(TX-,RX-).
If more than one frequency converter is con-
nected to a master, use parallel connections.
In order to avoid potential equalizing currents in the screen, earth the cable screen via terminal
61, which is connected to the frame via an RC-link.
Bus termination
The RS485 bus must be terminated by a resistor network at both ends. For this purpose, set switch
S801 on the control card for "ON".
For more information, see the paragraph
Switches S201, S202, and S801
.
NB!
Communication protocol must be set to FC MC par. 8-30.
5.5.2. How to Connect a PC to the FC 100
To control or program the frequency converter from a PC, install the MCT 10 Set-up Software.
The PC is connected via a standard (host/device) USB cable, or via the RS-485 interface as shown
in the FC 100 Design Guide chapter
How to Install > Installation of misc. connections
.
NB!
The USB connection is galvanically isolated from the supply voltage (PELV) and other
high-voltage terminals. The USB connection is connected to protection earth on the
frequency converter. Use only isolated laptop as PC connection to the USB connector
on the VLT HVAC Drive.
VLT
®
HVAC Drive Design Guide
5. How to Install
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
103