5.2.7. Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an in-
stallation, switch gear, machines etc., must be shortcircuit and overcurrent protected according
to the national/international regulations.
Short circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard.
Danfoss recommends using the fuses mentioned in tables 4.3 and 4.4 to protect service personnel
or other equipment in case of an internal failure in the unit. The frequency converter provides full
short circuit protection in case of a short-circuit on the motor output.
Over-current protection:
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation.
Over current protection must always be carried out according to national regulations. The fre-
quency converter is equipped with an internal over current protection that can be used for
upstream overload protection (UL-applications excluded). See par. 4-18. Fuses must be designed
for protection in a circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical), 500 V/
600 V maximum.
Non UL compliance
If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in table
4.2, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to
the frequency converter.
VLT HVAC
Max. fuse size
Voltage
Type
200-240 V
K25-1K1
16A
1
200-240 V
type gG
1K5
16A
1
200-240 V
type gG
2K2
25A
1
200-240 V
type gG
3K0
25A
1
200-240 V
type gG
3K7
35A
1
200-240 V
type gG
5K5
50A
1
200-240 V
type gG
7K5
63A
1
200-240 V
type gG
11K
63A
1
200-240 V
type gG
15K
80A
1
200-240 V
type gG
18K5
125A
1
200-240 V
type gG
22K
125A
1
200-240 V
type gG
30K
160A
1
200-240 V
type gG
37K
200A
1
200-240 V
type aR
45K
250A
1
200-240 V
type aR
380-500 V
11K
63A
1
380-480 V
type gG
15K
63A
1
380-480 V
type gG
18K
63A
1
380-480 V
type gG
22K
63A
1
380-480 V
type gG
30K
80A
1
380-480 V
type gG
37K
100A
1
380-480 V
type gG
45K
125A
1
380-480 V
type gG
55K
160A
1
380-480 V
type gG
75K
250A
1
380-480 V
type aR
90K
250A
1
380-480 V
type aR
Table 5.2: Non UL fuses 200 V to 500 V
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
VLT
®
HVAC Drive Design Guide
5. How to Install
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
91
5
Содержание VLT series
Страница 78: ...4 How to Order VLT HVAC Drive Design Guide 78 MG 11 B2 02 VLT is a registered Danfoss trademark 4...
Страница 120: ...7 RS 485 Installation and Set up VLT HVAC Drive Design Guide 120 MG 11 B2 02 VLT is a registered Danfoss trademark 7...
Страница 152: ...8 Troubleshooting VLT HVAC Drive Design Guide 152 MG 11 B2 02 VLT is a registered Danfoss trademark 8...