6. Application Examples
6.1.1. Start/Stop
Terminal 18 = start/stop par. 5-10 [8]
Start
Terminal 27 = No operation par. 5-12 [0]
No
operation
(Default
coast inverse
Par. 5-10
Digital Input
=
Start
(de-
fault)
Par. 5-12
Digital Input
=
coast in-
verse
(default)
Illustration 6.1: Terminal 37: Available only with
Safe Stop Function!
6.1.2. Pulse Start/Stop
Terminal 18 = start/stop par. 5-10 [9]
Latched
start
Terminal 27= Stop par. 5-12 [6]
Stop inverse
Par. 5-10
Digital Input
=
Latched
start
Par. 5-12
Digital Input
=
Stop in-
verse
Illustration 6.2: Terminal 37: Available only with
Safe Stop Function!
VLT
®
HVAC Drive Design Guide
6. Application Examples
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
111
6