13-51 SL Controller Event
Array [20]
Option:
Function:
[42]
Auto Reset Trip
[43]
OK Key
[44]
Reset Key
[45]
Left Key
[46]
Right Key
[47]
Up Key
[48]
Down Key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[76]
Digital Input x30 2
[77]
Digital Input x30 3
[78]
Digital Input x30 4
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
[92]
ECB Test Mode
[100] Fire Mode
See
13-15 RS-FF Operand S
,
13-16 RS-
FF Operand R
.
13-52 SL Controller Action
Array [20]
Option:
Function:
Select the action corresponding to the
SLC event. Actions are executed when
the corresponding event (defined in
parameter 13-51 SL Controller Event
) is
evaluated as true. The following actions
are available for selection:
[0]
Disabled
[1]
No action
[2]
Select set-up 1
Changes the active set-up
(
) to 1.
[3]
Select set-up 2
Changes the active set-up
(
) to 2.
[4]
Select set-up 3
Changes the active set-up
(
) to 3.
[5]
Select set-up 4
Changes the active set-up
(
) to 4. If the
set-up is changed, it merges with other
13-52 SL Controller Action
Array [20]
Option:
Function:
set-up commands coming from either
the digital inputs or via a fieldbus.
[10]
Select preset ref
0
Selects preset reference 0.
[11]
Select preset ref
1
Selects preset reference 1.
[12]
Select preset ref
2
Selects preset reference 2.
[13]
Select preset ref
3
Selects preset reference 3.
[14]
Select preset ref
4
Selects preset reference 4.
[15]
Select preset ref
5
Selects preset reference 5.
[16]
Select preset ref
6
Selects preset reference 6.
[17]
Select preset ref
7
Selects preset reference 7. If the active
preset reference is changed, it merges
with other preset reference commands
coming from either the digital inputs or
via a fieldbus.
[18]
Select ramp 1
Selects ramp 1.
[19]
Select ramp 2
Selects ramp 2.
[22]
Run
Issues a start command to the frequency
converter.
[23]
Run reverse
Issues a start reverse command to the
frequency converter.
[24]
Stop
Issues a stop command to the frequency
converter.
[26]
DC Brake
Issues a DC stop command to the
frequency converter.
[27]
Coast
The frequency converter coasts
immediately. All stop commands
including the coast command stop the
SLC.
[28]
Freeze output
Freezes the output frequency of the
frequency converter.
[29]
Start timer 0
Starts timer 0, see
for further description.
[30]
Start timer 1
Starts timer 1, see
for further description.
[31]
Start timer 2
Starts timer 2, see
for further description.
[32]
Set digital out
A low
Any output with digital output 1 selected
is low (off).
[33]
Set digital out B
low
Any output with digital output 2 selected
is low (off).
Parameter Descriptions
VLT
®
HVAC Drive FC 102
116
Danfoss A/S © 03/2015 All rights reserved.