6-23 Terminal 54 High Current
Range:
Function:
20 mA
*
[ par. 6-22 -
20 mA]
Enter the high current value
corresponding to the high reference/
feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value that
corresponds to the low voltage/low
current value set in
parameter 6-20 Terminal 54 Low Voltage
and
parameter 6-22 Terminal 54 Low
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value
that corresponds to the high voltage/
high current value set in
parameter 6-21 Terminal 54 High Voltage
and
parameter 6-23 Terminal 54 High
.
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10 s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise in
terminal 54. A high time constant value
improves dampening but also increases
the time delay through the filter.
6-27 Terminal 54 Live Zero
Option:
Function:
Disables the live zero-monitoring, for example if
the analog outputs are used as part of a
decentral I/O system (that is if these are used to
feed a building management system with data,
and not as part of any control functions related
to the frequency converter).
[0]
Disabled
[1]
*
Enabled
3.8.4 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for
analog input 3 (X30/11) placed on option module MCB
101.
6-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-31 V]
Sets the analog input scaling value to
correspond to the low reference/feedback
value (set in
).
6-31 Terminal X30/11 High Voltage
Range:
Function:
10 V
*
[ par. 6-30 -
10 V]
Sets the analog input scaling value to
correspond to the high reference/feedback
value (set in
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling value to
correspond to the low voltage value (set
in
parameter 6-30 Terminal X30/11 Low
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling value to
correspond to the high voltage value
(set in
parameter 6-31 Terminal X30/11
).
6-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal X30/11. A high value improves
dampening, but also increases the delay
through the filter.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
84