23-04 Occurrence
Array [10]
Option:
Function:
Select which day(s) the timed action
applies to. Specify working/non-working
days in
•
•
Parameter 0-82 Additional Working
Days
.
•
Parameter 0-83 Additional Non-
Working Days
[0]
*
All days
[1]
Working days
[2]
Non-working
days
[3]
Monday
[4]
Tuesday
[5]
Wednesday
[6]
Thursday
[7]
Friday
[8]
Saturday
[9]
Sunday
23-08 Timed Actions Mode
Used to enable and disable automatic timed actions.
Option:
Function:
[0]
*
Timed Actions Auto
Enable timed actions.
[1]
Timed Actions
Disabled
Disable timed actions, normal
operation according to control
commands.
[2]
Constant On Actions
Disable timed actions. Constant On
Actions activated.
[3]
Constant Off Actions
Disable timed actions. Constant Off
Actions activated.
23-09 Timed Actions Reactivation
Option:
Function:
[0]
Disabled After an update of time/condition
•
power cycling
•
setting date
•
time
•
change of summertime
•
change of Hand Auto mode
•
change of Constant ON and OFF
set-up change all activated ON actions are
overridden to OFF actions until passing the next
time for an ON action. Any OFF actions remain
unchanged.
23-09 Timed Actions Reactivation
Option:
Function:
[1]
*
Enabled After an update of time/condition On and OFF
actions are immediately set to the actual time
programming of ON and OFF actions.
To see an example of a reactivation test, see
Timed Action
ON: RUN
OFF: STOP
Power
Cycle
P23-09:
Disabled
Power
Cycle
P23-09:
Disabled
P23-09:
Disable
Enable
Power
Cycle
P23-09:
Enabled
Status
RUNNING
STOPPED
130BB808.10
Illustration 3.60 Reactivation Test Diagram
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
175
3