5-58
Term. 33 High Ref./Feedb. Value
100 N/A
All set-ups
TRUE
-3
Int32
5-59
Pulse Filter Time Constant #33
100 ms
All set-ups
FALSE
-3
Uint16
5-6* Pulse Output
5-60
Terminal 27 Pulse Output Variable
[0] No operation
All set-ups
TRUE
-
Uint8
5-62
Pulse Output Max Freq #27
5000 Hz
All set-ups
TRUE
0
Uint32
5-63
Terminal 29 Pulse Output Variable
[0] No operation
All set-ups
TRUE
-
Uint8
5-65
Pulse Output Max Freq #29
5000 Hz
All set-ups
TRUE
0
Uint32
5-66
Terminal X30/6 Pulse Output Variable
[0] No operation
All set-ups
TRUE
-
Uint8
5-68
Pulse Output Max Freq #X30/6
5000 Hz
All set-ups
TRUE
0
Uint32
5-8* I/O Options
5-80
AHF Cap Reconnect Delay
25 s
2 set-ups
TRUE
0
Uint16
5-9* Bus Controlled
5-90
Digital & Relay Bus Control
0 N/A
All set-ups
TRUE
0
Uint32
5-93
Pulse Out #27 Bus Control
0 %
All set-ups
TRUE
-2
N2
5-94
Pulse Out #27 Timeout Preset
0 %
1 set-up
TRUE
-2
Uint16
5-95
Pulse Out #29 Bus Control
0 %
All set-ups
TRUE
-2
N2
5-96
Pulse Out #29 Timeout Preset
0 %
1 set-up
TRUE
-2
Uint16
5-97
Pulse Out #X30/6 Bus Control
0 %
All set-ups
TRUE
-2
N2
5-98
Pulse Out #X30/6 Timeout Preset
0 %
1 set-up
TRUE
-2
Uint16
5.1.8 6-** Analog In / Out
Param
eter #
Parameter description
Default value
4 set-up
Change during
operation
Conversion
index
Type
6-0* Analog I/O Mode
6-00
Live Zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
6-01
Live Zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
6-02
Fire Mode Live Zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
6-1* Analog Input 53
6-10
Terminal 53 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-11
Terminal 53 High Voltage
10 V
All set-ups
TRUE
-2
Int16
6-12
Terminal 53 Low Current
4 mA
All set-ups
TRUE
-5
Int16
6-13
Terminal 53 High Current
20 mA
All set-ups
TRUE
-5
Int16
6-14
Terminal 53 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-15
Terminal 53 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-16
Terminal 53 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-17
Terminal 53 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
6-2* Analog Input 54
6-20
Terminal 54 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-21
Terminal 54 High Voltage
10 V
All set-ups
TRUE
-2
Int16
6-22
Terminal 54 Low Current
4 mA
All set-ups
TRUE
-5
Int16
6-23
Terminal 54 High Current
20 mA
All set-ups
TRUE
-5
Int16
6-24
Terminal 54 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-25
Terminal 54 High Ref./Feedb. Value
100 N/A
All set-ups
TRUE
-3
Int32
6-26
Terminal 54 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-27
Terminal 54 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
6-3* Analog Input X30/11
6-30
Terminal X30/11 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-31
Terminal X30/11 High Voltage
10 V
All set-ups
TRUE
-2
Int16
6-34
Term. X30/11 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-35
Term. X30/11 High Ref./Feedb. Value
100 N/A
All set-ups
TRUE
-3
Int32
6-36
Term. X30/11 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-37
Term. X30/11 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
6-4* Analog Input X30/12
Parameter Lists
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
229
5
5