13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[70]
SL Time-out 3
Use the result of timer 3 in the logic
rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic
rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic
rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic
rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic
rule.
[76]
Digital Input x30
2
[77]
Digital Input x30
3
[78]
Digital Input x30
4
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
[92]
ECB Test Mode
[100] Fire Mode
See
13-15 RS-FF Operand S
,
13-16 RS-FF
Operand R
.
13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
Select the first logical operator to use on the
boolean inputs from
and
Parameter numbers in square brackets stand
for the boolean inputs of parameters in group
13-** Smart Logic Control
.
[0] DISABLED
Ignores
•
Parameter 13-42 Logic Rule Boolean 2
.
•
Parameter 13-43 Logic Rule Operator 2
.
•
Parameter 13-44 Logic Rule Boolean 3
.
[1] AND
Evaluates the expression [13-40] AND [13-42].
[2] OR
Evaluates the expression [13-40] OR [13-42].
[3] AND NOT
Evaluates the expression [13-40] AND NOT
[13-42].
[4] OR NOT
Evaluates the expression [13-40] OR NOT
[13-42].
13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
[5] NOT AND
Evaluates the expression NOT [13-40] AND
[13-42].
[6] NOT OR
Evaluates the expression NOT [13-40] OR
[13-42].
[7] NOT AND
NOT
Evaluates the expression NOT [13-40] AND NOT
[13-42].
[8] NOT OR
NOT
Evaluates the expression NOT [13-40] OR NOT
[13-42].
13-42 Logic Rule Boolean 2
Array [6]
Option:
Function:
Select the second boolean (TRUE or
FALSE) input for the selected logic
rule.
See
for further descriptions of
options and their functions.
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
113
3
3
Содержание VLT HVAC Drive FC 102
Страница 1: ...Programming Guide VLT HVAC Drive FC 102 vlt drives danfoss com...
Страница 2: ......