5-65 Pulse Output Max Freq #29
Range:
Function:
5000 Hz
*
[0 - 32000
Hz]
Set the maximum frequency for terminal
29 corresponding to the output variable
set in
parameter 5-63 Terminal 29 Pulse
5-66 Terminal X30/6 Pulse Output Variable
Select the variable for readout on terminal X30/6.
This parameter is active when option module MCB 101 is
installed in the frequency converter.
Same options and functions as parameter group
5-6* Pulse
Outputs
.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Fe-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
5-68 Pulse Output Max Freq #X30/6
Range:
Function:
Size
related
*
[0 -
32000 Hz]
Select the maximum frequency on
terminal X30/6 referring to the output
variable in
.
This parameter is active when option
module MCB 101 is installed in the
frequency converter.
3.7.7 5-8* I/O Options
5-80 AHF Cap Reconnect Delay
Range:
Function:
25 s
*
[1 - 120
s]
Guarantees a minimum off-time for the
capacitors. The timer starts once the AHF
capacitor disconnects and needs to expire
before the output is allowed to be on again. It
only turns on again if the drive power is
between 20% and 30%.
3.7.8 5-9* Bus-Controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 -
2147483647 ]
This parameter holds the state of the digital
outputs and relays that is controlled by bus.
A logical '1' indicates that the output is high
or active.
A logical '0' indicates that the output is low
or inactive.
Bit 0
CC digital output terminal 27
Bit 1
CC digital output terminal 29
Bit 2
GPIO digital output terminal X
30/6
Bit 3
GPIO digital output terminal X
30/7
Bit 4
CC relay 1 output terminal
Bit 5
CC relay 2 output terminal
Bit 6
Option B relay 1 output terminal
Bit 7
Option B relay 2 output terminal
Bit 8
Option B relay 3 output terminal
Bit 9-15 Reserved for future terminals
Bit 16
Option C relay 1 output terminal
Bit 17
Option C relay 2 output terminal
Bit 18
Option C relay 3 output terminal
Bit 19
Option C relay 4 output terminal
Bit 20
Option C relay 5 output terminal
Bit 21
Option C relay 6 output terminal
Bit 22
Option C relay 7 output terminal
Bit 23
Option C relay 8 output terminal
Bit
24-31
Reserved for future terminals
Table 3.13 Digital Output Bits
5-93 Pulse Out #27 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Contains the frequency to apply to the
digital output terminal 27 when it is
configured as bus-controlled.
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] Contains the frequency to apply to the
digital output terminal 27, when it is
configured as bus-controlled time-out and
timeout is detected.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
80
Danfoss A/S © 03/2015 All rights reserved.
MG11CE02
3
3