1-77 Compressor Start Max Speed [RPM]
Range:
Function:
the time where the motor is operated under
the minimum speed for the application. The
time without protection from the current limit
and torque limit must not exceed the value
set in
parameter 1-79 Compressor Start Max
. If the value in
parameter 1-79 Compressor Start Max Time to
Trip
is exceeds, the frequency converter trips
with
alarm 18, Start failed
.
When this function is activated to get a fast
start,
parameter 1-86 Trip Speed Low [RPM]
is
also activated to protect the application from
running below minimum motor speed, for
example when in current limit.
This function allows high starting torque and
use of a fast starting ramp. To ensure the
build-up of a high torque during the start,
various tricks can be done through clever use
of start delay/start speed/start current.
1-78 Compressor Start Max Speed [Hz]
Range:
Function:
Size
related
*
[ 0 -
par.
4-14
Hz]
NOTICE
Parameter 1-78 Compressor Start Max
Speed [Hz]
has no have effect when
parameter 1-10 Motor Construction
PM, non-salient SPM.
The parameter enables high starting torque.
This is a function, where the current limit and
torque limit are ignored during start of the
motor. The time, from the start signal is given
until the speed exceeds the speed set in this
parameter, becomes a start-zone where the
current limit and motoric torque limit is set to
what is maximum possible for the frequency
converter/motor combination. This parameter
is normally set to the same value as
parameter 4-11 Motor Speed Low Limit [RPM]
When set to zero the function is inactive.
In this starting-zone,
is active instead of
parameter 3-41 Ramp 1 Ramp Up Time
to
ensure extra acceleration during the start, and
to minimise the time where the motor is
operated under the minimum speed for the
application. The time without protection from
the current limit and torque limit must not
exceed the value set in
parameter 1-79 Compressor Start Max Time to
Trip
.I the value of
is exceeded, the
frequency converter trips with
alarm 18 Start
failed
.
1-78 Compressor Start Max Speed [Hz]
Range:
Function:
When this function is activated to get a fast
start,
parameter 1-86 Trip Speed Low [RPM]
is
also activated to protect the application from
running below minimum motor speed, for
example when in current limit.
This function allows high starting torque and
use of a fast starting ramp. To ensure the
build-up of a high torque during the start,
various tricks can be done through clever use
of start delay/start speed/start current.
1-79 Compressor Start Max Time to Trip
Range:
Function:
5 s
*
[0 -
10 s]
NOTICE
Parameter 1-79 Compressor Start Max Time to
Trip
has no effect when
=[1] PM, non-salient SPM.
The time, from the start signal is given until the
speed exceeds the speed set in
parameter 1-77 Compressor Start Max Speed [RPM]
must not exceed the time set in the parameter. If
the time set is exceeded the frequency converter
trips with
Alarm 18, Start failed
.
Any time set in
for use of
a start function must be executed within the time
limit.
Parameter Descriptions
Programming Guide
MG11CE02