3.2.4 0-3* LCP Custom Readout
It is possible to customise the display elements for various
purposes:
•
Custom Readout. Value proportional to speed
(linear, squared or cubed depending on unit
selected in
parameter 0-30 Custom Readout Unit
).
•
Display Text. Text string stored in a parameter.
Custom readout
The calculated value to be displayed is based on the
settings in:
•
Parameter 0-30 Custom Readout Unit
•
Parameter 0-31 Custom Readout Min Value
(linear
only).
•
Parameter 0-32 Custom Readout Max Value
.
•
Parameter 4-13 Motor Speed High Limit [RPM]
.
•
Parameter 4-14 Motor Speed High Limit [Hz]
•
Actual speed.
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
P 0-31
Linear
units only
Quadr
atic Unit (P
ressur
e)
Cubic Unit (P
ow
er)
Motor Speed
Motor Speed
High limit
P 4-13 (RPM)
P 4-14 (Hz)
0
130B
T105.12
Lin
ear
Un
it (e
.g. s
pe
ed
an
d fl
ow
)
Illustration 3.3 Custom Readout
The relation depends on the type of unit selected in
parameter 0-30 Custom Readout Unit
:
Unit type
Speed relation
Dimensionless
Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Quadratic
Power
Cubic
Table 3.3 Speed Relations for Different Unit Types
0-30 Custom Readout Unit
Option:
Function:
Programme a value to be shown in the LCP
display. The value has a linear, squared or cubed
relation to speed. This relation depends on the
unit selected (see
). The actual calculated
value can be read in
, and/or shown in the display by selecting
[1609 Custom Readout]
in
to
0-24 Display Line 3 Large
.
[0]
None
[1]
*
%
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
Parameter Descriptions
VLT
®
HVAC Drive FC 102
32
Danfoss A/S © 03/2015 All rights reserved.
MG11CE02
3
3