WARNING 200, Fire mode
This warning indicates that the frequency converter is
operating in fire mode. The warning clears when fire mode
is removed. See the fire mode data in the alarm log.
WARNING 201, Fire mode was active
This indicates that the frequency converter has entered fire
mode. Cycle power to the unit to remove the warning. See
the fire mode data in the alarm log.
WARNING 202, Fire mode limits exceeded
While operating in fire mode, 1 or more alarm conditions
have been ignored which would normally trip the unit.
Operating in this condition voids unit warranty. Cycle
power to the unit to remove the warning. See the fire
mode data in the alarm log.
WARNING 203, Missing motor
With a frequency converter operating multi-motors, an
underload condition was detected. This could indicate a
missing motor. Inspect the system for proper operation.
WARNING 204, Locked rotor
With a frequency converter operating multi-motors, an
overload condition was detected. This could indicate a
locked rotor. Inspect the motor for proper operation.
WARNING 250, New spare part
A component in the frequency converter has been
replaced.
Troubleshooting
•
Reset the frequency converter for normal
operation.
WARNING 251, New typecode
The power card or other components have been replaced
and the type code has been changed.
Troubleshooting
•
Reset to remove the warning and resume normal
operation.