2.4 Programming Parameters
Procedure:
1.
Press [Menu] until the arrow in the display
indicates the wanted menu:
Quick Menu
or
Main
Menu
.
2.
To browse through the parameter groups, press
[
▲
] [
▼
].
3.
To select a parameter group, press [OK].
4.
To browse through the parameters in the specific
group, press [
▲
] [
▼
].
5.
To select the parameter, press [OK].
6.
To change the parameter value, press [
▲
] [
▼
] [
▶
].
7.
To save the new setting, press [OK]. To abort,
press [Back].
8.
To return to the previous menu, press [Back].
2.5 Back-up and Copying Parameter
Settings
NOTICE
Stop the motor before backing-up or copying parameter
settings.
Data storage in LCP
Once the set-up of a frequency converter is complete,
store the data in the LCP. Alternatively, use a PC with the
MCT 10 Set-up Software to perform the same back-up.
1.
Go to
2.
Press [OK].
3.
Select
[1] All to LCP
.
4.
Press [OK].
Data transfer from LCP to frequency converter
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
1.
Go to
2.
Press [OK].
3.
Select
[2] All from LCP
.
4.
Press [OK].
2.6 Restoring Default Settings
Select initialization mode according to the requirement for
retaining parameter settings.
Recommended initialization
(via
parameter 14-22 Operation Mode
Use this method to initialize the frequency converter
without resetting communication settings.
1.
Select
parameter 14-22 Operation Mode
.
2.
Press [OK].
3.
Select
[2] initialization
and Press [OK].
4.
Cut off the mains supply and wait until the
display turns off.
5.
Reconnect the mains supply.
The frequency converter is now reset, except for the
following parameters:
•
Parameter 0-03 Regional Settings
.
•
Parameter 8-30 Protocol
.
•
Parameter 8-31 Address
.
•
Parameter 8-32 Baud Rate
.
•
Parameter 8-33 Parity / Stop Bits
.
•
Parameter 8-35 Minimum Response Delay
.
•
Parameter 8-36 Maximum Response Delay
.
•
Parameter 8-70 BACnet Device Instance
•
Parameter 8-72 MS/TP Max Masters
•
Parameter 8-73 MS/TP Max Info Frames
.
•
•
Parameter 8-75 Intialisation Password
•
Parameter 15-00 Operating hours
.
•
.
•
•
•
Parameter 15-30 Alarm Log: Error Code
•
Parameter group 15-4* Drive identification
parameters
.
•
Parameter 1-06 Clockwise Direction
.
Programming
Programming Guide
MG03N202