5.4 Extended Status Words
Bit
Hex
Dec
Parameter 16-95 Ext. Status Word 2
0
1
1
Ramping
Off
1
2
2
AMA running
Hand/Auto
2
4
4
Start CW/CCW
1)
3
8
8
1)
1)
4
10
16
1)
1)
5
20
32
Feedback high
1)
6
40
64
Feedback low
1)
7
80
128
Output current high
Control Ready
8
100
256
Output current low
Drive Ready
9
200
512
Output frequency high
Quick Stop
10
400
1024
Output frequency low
DC Brake
11
800
2048
1)
Stop
12
1000
4096
1)
1)
13
2000
8192
Braking
Freeze Output Request
14
4000
16384
1)
Freeze Output
15
8000
32768
OVC active
Jog Request
16
10000
65536
AC brake
Jog
17
20000
131072
1)
Start request
18
40000
262144
1)
Start
19
80000
524288
Reference high
1)
20
100000
1048576
Reference low
Start Delay
21
200000
2097152
Local Ref./Remote Ref.
Sleep
22
400000
4194304
1)
Sleep boost
23
800000
8388608
1)
Running
24
1000000
16777216
1)
Bypass
25
2000000
33554432
1)
Fire Mode
26
4000000
67108864
1)
External Interlock
27
8000000
134217728
1)
Firemodelimitexceed
28
10000000
268435456
1)
FlyStart Active
29
20000000
536870912
1)
1)
30
40000000
1073741824
1)
1)
31
80000000
2147483648
Database busy
1)
Table 5.5 Extended Status Words
1) This alarm is not used in FCP 106.
Diagnostics and Troubleshoo...
VLT
®
DriveMotor FCP 106/FCM 106
122
Danfoss A/S © 11/2015 All rights reserved.
MG03N202
5
5