1-11 Motor Selection
Option:
Function:
Setting the parameter value might
change these parameters. Other
parameters also change, when
changing motor type selection.
[1]
Motor Selection 1
[2]
Motor Selection 2
[3]
Motor Selection 3
[4]
Motor Selection 4
[5]
Motor Selection 5
[6]
Motor Selection 6
[7]
Motor Selection 7
[8]
Motor Selection 8
[9]
Motor Selection 9
[10] Motor Selection 10
[11] Motor Selection 11
[12] Motor Selection 12
[13] Motor Selection 13
[14] Motor Selection 14
[15] Motor Selection 15
[16] Motor Selection 16
[17] Motor Selection 17
[18] Motor Selection 18
[19] Motor Selection 19
[20] Motor Selection 20
[21] Motor Selection 21
[22] Motor Selection 22
[23] Motor Selection 23
[24] Motor Selection 24
[25] Motor Selection 25
[26] Motor Selection 26
[27] Motor Selection 27
[28] Motor Selection 28
[29] Motor Selection 29
[30] Motor Selection 30
[31] Motor Selection 31
[32] Motor Selection 32
[33] Motor Selection 33
[34] Motor Selection 34
[35] Motor Selection 35
[36] Motor Selection 36
[37] Motor Selection 37
[38] Motor Selection 38
[39] Motor Selection 39
[40] Motor Selection 40
[41] Motor Selection 41
[42] Motor Selection 42
[43] Motor Selection 43
[44] Motor Selection 44
[45] Motor Selection 45
[46] Motor Selection 46
[47] Motor Selection 47
[48] Motor Selection 48
1-11 Motor Selection
Option:
Function:
[49] Motor Selection 49
[50] Motor Selection 50
[51] Motor Selection 51
[52] Motor Selection 52
[53] Motor Selection 53
[54] Motor Selection 54
[55] Motor Selection 55
[56] Motor Selection 56
[57] Motor Selection 57
[58] Motor Selection 58
[59] Motor Selection 59
[60] Motor Selection 60
[61] Motor Selection 61
[62] Motor Selection 62
[63] Motor Selection 63
[64] Motor Selection 64
1-12 Motor ID
Range:
Function:
Default
Motor
*
[0 - 0 ] Shows motor name according to the
selected motor in
4.2.3 1-14 to 1-17 VVC
+
PM
The default control parameters for VVC
+
PM motor control
core are optimized for HVAC applications and inertia load
in the range of 50>Jl/Jm>5. Jl is load inertia from the
application and Jm is machine inertia.
For low inertia applications (Jl/Jm<5), it is recommended
that
parameter 1-17 Voltage filter time const.
is increased
with a factor of 5–10. Sometimes,
parameter 14-08 Damping Gain Factor
should also be
reduced to improve performance and stability.
For high inertia applications (Jl/Jm>50), it is recommended
that
parameter 1-15 Low Speed Filter Time Const.
,
parameter 1-16 High Speed Filter Time Const.
, and
parameter 14-08 Damping Gain Factor
are increased to
improve performance and stability.
For high load at low speed (<30% of rated speed), it is
recommended that
parameter 1-17 Voltage filter time const.
is increased due to non-linearity in the inverter at low
speed.
1-14 Damping Gain
Range:
Function:
120
%
*
[0 -
250 %]
The parameter stabilizes the PM motor to ensure
smooth and stable operation. The value of
damping gain controls the dynamic performance
of the PM motor. Low damping gain results in
high dynamic performance and a high value
results in a low dynamic performance. The
dynamic performance is related to the motor data
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
42
Danfoss A/S © 11/2015 All rights reserved.
MG03N202
4
4