0-30 Custom Readout Unit
Option:
Function:
be read in
.
[0]
None
[1]
*
%
[5]
PPM
[10]
l/Min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m3/s
[24]
m3/min
[25]
m3/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
Degree Celsius
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m Wg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[127] ft3/h
[140] ft/s
[141] ft/min
[160] Degree Fahr
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] hp
0-31 Custom Readout Min Value
Range:
Function:
0 CustomRea-
doutUnit
*
[ 0 -
999999.99
CustomRea-
doutUnit]
This parameter sets the
minimum value of the custom-
defined readout (occurs at 0
speed). It is only possible to
select a value different from 0
when selecting a linear unit in
0-31 Custom Readout Min Value
Range:
Function:
parameter 0-30 Custom Readout
Unit
. For quadratic and cubic
units, the minimum value is 0.
0-32 Custom Readout Max Value
Range:
Function:
100 Custom-
ReadoutUnit
*
[ 0.0 -
999999.99
CustomRea-
doutUnit]
This parameter sets the
maximum value to be shown
when the speed of the motor
has reached the set value for
parameter 4-14 Motor Speed
High Limit [Hz]
0-37 Display Text 1
Range:
Function:
[0 - 0 ] Use this parameter to write an individual text string
to be read via serial communication. Device ID can
be included.
Only used when running BACnet.
0-38 Display Text 2
Range:
Function:
[0 - 0 ] Use this parameter to write an individual text string
to be read via serial communication.
Only used when running BACnet.
0-39 Display Text 3
Range:
Function:
[0 - 0 ] Use this parameter to write an individual text string
to be read via serial communication.
Only used when running BACnet.
4.1.4 0-4* LCP
Enable, disable, and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled To avoid unintended start of the frequency
converter in
local mode
, select
[0] Disabled
.
[1]
*
Enabled [Hand On] is enabled.
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled To avoid unintended start of the frequency
converter from the LCP, select
[0] Disabled
.
[1]
*
Enabled [Auto On] is enabled.
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
38
Danfoss A/S © 11/2015 All rights reserved.
MG03N202
4