Field name
Example (hex)
Slave address
01
Function
10
Starting address HI
04
Starting address LO
19
Number of registers HI
00
Number of registers LO
02
Error check (CRC)
–
Table 3.23 Response
3.10.4 Read/Write Multiple registers (17
hex)
Description
This function code combines 1 read operation and 1 write
operation in a single Modbus transaction. The write
operation is performed before the read.
Query
The query message specifies the starting address and
number of holding registers to be read as well as the
starting address, number of holding registers, and the data
to be written. Holding registers are addressed starting at 0.
Example of a request to set
parameter 1-24 Motor Current
to 738 (7.38 A) and read
which has value 50000 (50000 Hz):
Field name
Example (hex)
Follower Address
01
Function
17
Read Starting Address HI
0B (Register address 3029)
Read Starting Address LO
D5 (Register address 3029)
Quantity to Read HI
00
Quantity to Read LO
02
(
is 32 bits long,
that is, 2 registers)
Write Starting Address HI
04 (Register address 1239)
Write Starting address LO
D7 (Register address 1239)
Quantity to Write HI
00
Quantity to Write LO
02
Write Byte Count
04
Write Registers Value HI
00
Write Registers Value LO
00
Write Registers Value HI
02
Write Registers Value LO
0E
Error Check (CRC)
–
Table 3.24 Query
Response
The normal response contains the data from the group of
registers that were read. The byte count field specifies the
quantity of bytes to follow in the read data field.
Field name
Example (hex)
Follower Address
01
Function
17
Byte Count
04
Read Registers Value HI
00
Read Registers Value LO
00
Read Registers Value HI
C3
Read Registers Value LO
50
CRC
–
Table 3.25 Response
3.11 FC Control Profile
3.11.1 Control Word According to FC Profile
(8–10 Protocol = FC profile)
Speed ref.
CTW
Master-follower
130BA274.11
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
no.:
Illustration 3.20 Control Word According to FC Profile
Bit
Bit value=0
Bit value=1
00
Reference value
External selection lsb
01
Reference value
External selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output
frequency
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
Relay 01 open
Relay 01 active
12
Relay 02 open
Relay 02 active
13
Parameter set-up
Selection lsb
15
No function
Reverse
Table 3.26 Control Word According to FC Profile
Explanation of the control bits
Bits 00/01
Bits 00 and 01 are used to select among the 4 reference
values, which are pre-programmed in
according to
.
RS485 Installation and Set-...
VLT
®
DriveMotor FCP 106/FCM 106
30
Danfoss A/S © 11/2015 All rights reserved.
MG03N202