Call-
out
Indicator Light
Function
15
ON
Green
The ON light activates when the
frequency converter receives
power from mains voltage, a DC
bus terminal, or a 24 V external
supply.
16
WARN
Yellow
When warning conditions are
met, the yellow WARN light
turns on, and text appears in
the display area identifying the
problem.
17
ALARM
Red
A fault condition causes the red
alarm light to flash, and an
alarm text is shown.
Table 2.4 Legend to
D. Operation keys and indicator lights (LEDs)
Operation keys are at the bottom of the GLCP.
Callout Key
Function
18
Hand On
Starts the frequency converter in local
control.
•
An external stop signal by control
input or serial communication
overrides the local hand on.
19
Off
Stops the motor but does not remove
power to the frequency converter.
20
Auto On
Puts the system in remote operational
mode.
•
Responds to an external start
command by control terminals or
serial communication.
21
Reset
Resets the frequency converter manually
after a fault has been cleared.
Table 2.5 Legend to
NOTICE
To adjust the display contrast, press [Status] and [
▲
]/[
▼
].
2.3 GLCP Menus
2.3.1 Status Menu
In the
Status
menu, the selection options are:
•
Motor frequency [Hz],
•
Motor current [A],
.
•
Motor speed reference in percentage [%],
•
Feedback,
parameter 16-52 Feedback[Unit]
•
Motor power
for kW,
for hp. If
parameter 0-03 Regional Settings
is set to
[1] North
America
, motor power is shown in hp instead of
kW.
•
Custom readout
parameter 16-09 Custom Readout
2.3.2 Quick Menu
Use the Quick Menu to program the most common
functions. The Quick Menu consists of:
•
Wizard for open-loop applications. See
chapter 2.3.4 Configuration for Open-loop
Applications
for details.
•
Wizard for closed-loop applications. See
chapter 2.3.5 Set-up Wizard for Closed-loop
Applications
for details.
•
Motor set-up. See
chapter 2.3.6 Quick Menu Motor
for details.
•
Changes made.
2.3.3 Main Menu
The
Main Menu
is used for access to and programming of
all parameters. The
Main Menu
parameters can be accessed
readily unless a password has been created via
parameter 0-60 Main Menu Password
.
For most applications, it is not necessary to access the
Main Menu
parameters. Instead the
Quick Menu
provides
the simplest and quickest access to the parameters which
are typically required.
2.3.4 Configuration for Open-loop
Applications
This section guides the installer through the set-up of the
frequency converter in a clear and structured manner to
set up an open-loop application. An open-loop application
does not utilize a feedback signal from the process.
FC
+24 V (OUT)
DIG IN
DIG IN
DIG IN
DIG IN
COM DIG IN
A OUT / D OUT
A OUT / D OUT
18
19
27
29
42
55
50
53
54
20
12
01
02
03
04
05
06
R2
R1
+
-
0–10 V
Start
+10 V (OUT)
A IN
A IN
COM IN/OUT
130BB67
4.11
45
Reference
Illustration 2.2 Principle Wiring for Open-loop Applications
Programming
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.