0-44 [Off/Reset] Key on LCP
Option:
Function:
[0]
Disabled
Disable the off/reset key.
[1]
*
Enabled
Enable both off and reset functions.
[7]
Enable Reset
Only
Enable the reset function, and disable the
off function to avoid unintended stop of
the frequency converter.
4.1.5 0-5* Copy/Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups from the
frequency converter memory to the LCP
memory. For service purposes, copy all
parameters to the LCP after commissioning.
[2]
All from LCP Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3]
Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. The latter
selection can be used to program several
frequency converters with the same function
without disturbing motor data that is already
set.
[10] Delete LCP
copy data
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function
[1]
Copy from
setup 1
Copy from set-up 1 to set-up 2.
[2]
Copy from
setup 2
Copy from set-up 2 to set-up 1.
[9]
Copy from
Factory setup
Copy factory setting to programming set-
up (selected in
4.1.6 0-6* Password
0-60 Main Menu Password
Range:
Function:
0
*
[0 - 999 ] Define the password for access to the
Main Menu
via the [Main Menu] key. Setting the value to 0
disables the password function.
Parameters
Programming Guide
MG03N202