6-71 Terminal 45 Analog Output
Option:
Function:
[100] Output
frequency
0–100 Hz
[101] Reference
Min
Ref.
–Max
Ref.
[102] Feedback
Min
FB
–Max
FB
[103] Motor Current
0–I
max
[106] Power
0–P
nom
[139] Bus Control
0–100%
6-72 Terminal 45 Digital Output
Option:
Function:
Select the function of
terminal 45 as a digital
current output. See also
parameter 6-70 Terminal 45
Mode
. See
parameter 5-40 Function
Relay
for description of the
options.
[0]
*
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
Drive running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal
warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[32]
Mech brake ctrl
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
6-72 Terminal 45 Digital Output
Option:
Function:
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[191] Dry Pump
[192] End Of Curve
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-73 Terminal 45 Output Min Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scale for the minimum output (0 mA or 4 mA)
of the analog signal at terminal 45. Set the
value to be the percentage of the full range of
the variable selected in
.
6-74 Terminal 45 Output Max Scale
Range:
Function:
100
%
*
[0 -
200 %]
Scale for the maximum output (20 mA) of the
analog signal at terminal 45. Set the value to be
the percentage of the full range of the variable
selected in
parameter 6-71 Terminal 45 Analog
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
68