6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.01 s
*
[0.01 - 10
s]
Enter the time constant. This constant is a
first-order digital low-pass filter time
constant for suppressing electrical noise in
terminal 53. A high time constant value
improves dampening, but also increases the
time delay through the filter.
6-19 Terminal 53 mode
Option:
Function:
Select whether terminal 53 is used for
current or voltage input.
[0]
Current mode
[1]
*
Voltage mode
4.7.3 6-2* Analog Input 54
Parameters for configuring the scaling and limits for analog
input 54 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[0 - 10
V]
Enter the voltage (V) that corresponds to the
low reference value (set in
parameter 6-24 Terminal 54 Low Ref./Feedb.
Value
). To activate
, set the value at >1 V.
6-21 Terminal 54 High Voltage
Range:
Function:
10 V
*
[0 - 10 V] Enter the voltage (V) that corresponds to the
high reference value (set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value
6-22 Terminal 54 Low Current
Range:
Function:
4 mA
*
[0 - 20
mA]
Enter the low current value. This reference
signal corresponds to the low reference/
feedback value, set in
. To activate the live
zero timeout function in
, set the value to >2 mA.
6-23 Terminal 54 High Current
Range:
Function:
20 mA
*
[0 - 20
mA]
Enter the high current value corresponding
to the high reference/feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value
.
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0
*
[-4999 -
4999 ]
Enter the reference or feedback value that
corresponds to the voltage or current set in
parameter 6-21 Terminal 54 High Voltage
parameter 6-22 Terminal 54 Low Current
.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-4999 -
4999 ]
Enter the reference or feedback value
that corresponds to the voltage or
current set in
parameter 6-23 Terminal 54 High
Current
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.01 s
*
[0.01 - 10
s]
Enter the time constant, which is a first-
order digital low-pass filter time constant
for suppressing electrical noise in terminal
54. A high time constant value improves
dampening, but also increases the time
delay through the filter.
6-29 Terminal 54 mode
Option:
Function:
Select if terminal 54 is used for current
input or voltage input.
[0]
Current mode
[1]
*
Voltage mode
4.7.4 6-7* Analog/Digital Output 45
Parameters for configuring the scaling and limits for
analog/digital output terminal 45. Analog outputs are
current outputs: 0/4–20 mA. Resolution on analog output
is 12 bit. Analog output terminals can also be set up as
digital output.
6-70 Terminal 45 Mode
Option:
Function:
Set terminal 45 to act as analog output or
as digital output.
[0]
*
0-20 mA
[1]
4-20 mA
[2]
Digital Output
6-71 Terminal 45 Analog Output
Option:
Function:
Select the function of terminal 45 as an
analog current output. See also
parameter 6-70 Terminal 45 Mode
[0]
*
No operation
Parameters
Programming Guide
MG03N202