8-57 Profidrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-58 Profidrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
4.8.6 8-7* BACnet
8-70 BACnet Device Instance
Range:
Function:
1
*
[0 - 4194303 ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range:
Function:
127
*
[0 - 127 ] Define the address of the master, which holds
the highest address in this network. Decreasing
this value optimizes polling for the token.
8-73 MS/TP Max Info Frames
Range:
Function:
1
*
[1 - 65534 ] Define how many info/data frames the device
is allowed to send while holding the token.
8-74 "I am" Service
Option:
Function:
[0]
*
Send at
power-up
Select when the device should send the I-
Am service message only at power-up.
[1]
Continuously
Select when the device should send the I-
Am service message continuously with an
interval of approximately 1 minute.
8-75 Intialisation Password
Range:
Function:
admin
*
[1 - 1 ] Enter the password needed for execution of
Drive Re-initialization from BACnet.
8-79 Protocol Firmware version
Range:
Function:
Size related
*
[0 - 65535 ] Read the supported protocol version.
Index 5 is for BACnet.
4.8.7 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the FC port.
8-80 Bus Message Count
Range:
Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
valid telegrams detected on the bus.
8-81 Bus Error Count
Range:
Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
telegrams with faults (for example, CRC
fault), detected on the bus.
8-82 Slave Messages Rcvd
Range:
Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
valid telegrams addressed to the slave,
sent by the frequency converter.
8-83 Slave Error Count
Range:
Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
error telegrams, which the frequency
converter could not execute.
8-84 Slave Messages Sent
Range:
Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
messages sent from the slave.
8-85 Slave Timeout Errors
Range:
Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
slave timeout errors.
8-88 Reset FC port Diagnostics
Option:
Function:
[0]
*
Do not reset
[1]
Reset counter
Parameters