4.6.5 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminal 29 acts as frequency reference
inputs. Set terminal 29 (
parameter 5-13 Terminal 29 Digital
Input
to
[32] Pulse input
.
Ref.
(RPM)
High
ref.
value
P 5-53
Low
ref.
value
P 5-52
Low freq.
P 5-50
High freq.
P 5-51
Input
(Hz)
195NA453.10
Illustration 4.12 Pulse Input
5-50 Term. 29 Low Frequency
Range:
Function:
20 Hz
*
[20 -
31999 Hz]
Enter the low frequency limit
corresponding to the low motor shaft
speed (that is low reference value) in
parameter 5-52 Term. 29 Low Ref./Feedb.
Value
. Refer to
5-51 Term. 29 High Frequency
Range:
Function:
32000
Hz
*
[21 -
32000 Hz]
Enter the high frequency limit
corresponding to the high motor shaft
speed (that is high reference value) in
parameter 5-53 Term. 29 High Ref./Feedb.
Value
.
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0
*
[-4999 -
4999 ]
Enter the low reference value limit for the
motor shaft speed [RPM]. This value is also the
lowest feedback value, see also
parameter 5-13 Terminal 29 Digital Input
=
[32]
Pulse Input
.
5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-4999 -
4999 ]
Enter the high reference value [RPM]
for the motor shaft speed and the high
feedback value, see also
parameter 5-13 Terminal 29 Digital Input
=
[32] Pulse Input
.
4.6.6 5-9* Bus Controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 - 0xFFFFFFFF ] This parameter holds the state of the
digital outputs and relays controlled by
bus.
A logical 1 indicates that the output is
high or active.
A logical 0 indicates that the output is
low or inactive.
Bit 0–3
Reserved
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6–23
Reserved
Bit 24
Terminal 42 digital output
Bit 25
Terminal 45 digital output
Bit 26–31
Reserved
Table 4.6 Bit Functions
Parameters