4.8.3 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
Select the protocol for the integrated RS485
port. Change of settings in
may change the baud
rate.
[0]
*
FC
Communication according to the FC Protocol.
[2]
Modbus
RTU
Communication according to the Modbus RTU
protocol.
[4]
FLN
[5]
BACNet
8-31 Address
Range:
Function:
1
*
[ 0.0 - 247 ] Enter the address for the RS485 port. Valid
range: 1–126 for FC-bus, or 1–247 for Modbus.
8-32 Baud Rate
Option:
Function:
Select the baud rate for the RS485 port
Default refers to the FC protocol. Changing the
protocol in
parameter 8-30 Protocol
may
change the baud rate.
Changing protocol in
parameter 8-30 Protocol
may change the baud rate.
[0] 2400 Baud
[1] 4800 Baud
Default setting for FLN.
[2] 9600 Baud
Default setting for BACnet.
[3] 19200 Baud
Default setting for Modbus RTU.
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 Parity / Stop Bits
Option:
Function:
Parity and stop bits for the protocol
using the FC port. For some of the
protocols, not all options are available.
Default refers to the FC protocol.
Changing protocol in
parameter 8–30
Protocol
may change the baud rate.
[0] Even Parity, 1 Stop
Bit
[1] Odd Parity, 1 Stop
Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop
Bits
8-35 Minimum Response Delay
Range:
Function:
0.01 s
*
[ 0.0010 - 0.5
s]
Specify the minimum delay time
between receiving a request and
transmitting a response. This minimum
delay time is used for overcoming
modem turnaround delays.
8-36 Maximum Response Delay
Range:
Function:
Size
related
*
[ 0.1 -
10.0 s]
Specify the maximum permissible
delay time between receiving a
request and transmitting the response.
If this time is exceeded, no response is
returned.
8-37 Maximum Inter-char delay
Range:
Function:
0.025 s
*
[0.025 - 0.025
s]
Specify the maximum permissible time
interval between receipt of 2 bytes.
This parameter activates timeout if
transmission is interrupted.
4.8.4 8-4* MC Protocol Set
8-40 Telegram Selection
Option:
Function:
Enables use of freely configurable
telegrams or standard telegrams for
the FC Port.
[1]
*
Standard telegram 1
[300] Standard telegram
FCM300
8-42 PCD Write Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs.
The number of PCDs depends on the PPO type.
The values in PCD 3–10 are written to the selected parameters as
data values.
Option:
Function:
[0]
None
[1]
[302] Minimum Reference
[2]
[303] Maximum Reference
[3]
[341] Ramp 1 Ramp up time
[4]
[342] Ramp 1 Ramp down time
[5]
[351] Ramp 2 Ramp up time
[6]
[352] Ramp 2 Ramp down time
[7]
[380] Jog Ramp Time
[8]
[381] Quick Stop Time
[9]
[412] Motor Speed Low Limit
[Hz]
[10]
[414] Motor Speed High Limit
[Hz]
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
72
Danfoss A/S © 11/2015 All rights reserved.
MG03N202