Parameter
332
333
334
335
Digital input on terminal no.
2
3
4
5
Settings
No function
(NO OPERATION)
[0]
[0]
[0]
[0]
Reset
(RESET)
[1]
[1]
[1]
[1]
Coasting stop, inverse
(MOTOR COAST INVERSE)
[2]
[2]
[2]
[2]
Reset and coasting stop, inverse
(RESET & COAST INV.)
[3]
[3]
[3]
[3]
Quick-stop, inverse
(QUICK STOP INVERSE)
[4]
[4]
[4]
[4]
DC-braking, inverse
(DC-BRAKE INVERSE)
[5]
[5]
[5]
[5]
Stop inverse
(STOP INVERSE)
[6]
[6]
[6]
[6]
Start
(START)
[7]
[7]
[7]
[7]
Latched start
(LATCHED START)
[8]
[8]
[8]
[8]
Reversing
(REVERSING)
[9]
[9]
[9]
[9]
Start reversing
(START REVERSING)
[10]
[10]
[10]
[10]
Start clockwise, on
(ENABLE FORWARD)
[11]
[11]
[11]
[11]
Start counter-clockwise, on
(ENABLE REVERSE)
[12]
[12]
[12]
[12]
Jog
(JOGGING)
[13]
[13]
[13]
[13]
Freeze reference
(FREEZE REFERENCE)
[14]
[14]
[14]
[14]
Freeze output
(FREEZE OUTPUT)
[15]
[15]
[15]
[15]
Speed up
(SPEED UP)
[16]
[16]
[16]
[16]
Speed down
(SPEED DOWN)
[17]
[17]
[17]
[17]
Selection of Setup
(SETUP SELECT)
[18]
[18]
[18]
[18]
Catch-up
(CATCH UP)
[19]
[19]
[19]
[19]
Slow-down
(SLOW DOWN)
[20]
[20]
[20]
[20]
Preset reference
(PRESET REF.)
[21]
[21]
[21]
[21]
Preset reference, on
(PRESET REF. ON)
[22]
[22]
[22]
[22]
Precise stop, inverse
(PRECISE STOP)
[23]
Pulse reference
(PULSE REFERENCE)
[24]
Pulse feedback
(PULSE FEEDBACK)
[25]
Analogue reference
(REFERENCE)
[30]
Analogue feedback
(FEEDBACK)
[31]
Reset and start
(RESET AND START)
[32]
[32]
[32]
[32]
Freeze reference and start
(FREEZE REF AND START)
[33]
[33]
[33]
[33]
Ramp 2
(RAMP 2)
[34]
[34]
[34]
[34]
Start-ref bit 1
(START-REF BIT 1)
[35]
[35]
[35]
[35]
Start-ref bit 2
(START-REF BIT 2)
[36]
[36]
[36]
[36]
Start-ref bit 3
(START-REF BIT 3)
[37]
[37]
[37]
[37]
Table 3.11
Function:
In parameters 332-335 it is possible to choose between the
different possible functions related to the inputs on
terminals 2-5. The function options are shown in
Description of choice:
No function
is selected if the FC motor is not to react to
signals transmitted to the terminal.
Reset
zeroes the FC motor after an alarm; however, not all
alarms can be reset without disconnecting from mains.
Coasting stop, inverse
is used for making the FC motor run
freely to stop. Logic '0' leads to coasting stop.
Reset and coasting stop, inverse,
is used for activating
coasting stop at the same time as reset.
Logic ‘0’ leads to coasting stop and reset.
Quick stop, inverse
is used for stopping the motor in
accordance with the quick-stop ramp (set in parameter
212).
Logic '0' leads to a quick-stop.
DC breaking, inverse
is used for stopping the motor by
energizing it with a DC voltage for a given time, see
parameters 126-132.
Note that this function is only active if the settings of
parameters 126-132 is different from 0. Logic '0' leads to
DC braking.
Stop inverse
is activated by interrupting the voltage to the
terminal. This means that if the terminal has no voltage,
Programming
VLT
®
DriveMotor FCM Series
MG03BA02 - VLT
®
is a registered Danfoss trademark
49
3
3
Содержание VLT Brook Crompton Motor FCM 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Brook Crompton Motor FCM 300 www danfoss com drives...
Страница 2: ......
Страница 26: ...Illustration 2 5 Installation VLT DriveMotor FCM Series 24 MG03BA02 VLT is a registered Danfoss trademark 2 2...
Страница 37: ...Programming VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 35 3 3...
Страница 101: ...Index VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 99...
Страница 102: ...www danfoss com drives MG03BA02 175R0087 MG03BA02 Rev 2011 12 22...