for a period longer than the time set in parameter 317, the
function selected in parameter 318 will be activated.
Description of choice:
Set the desired time.
318
Function after time out
Value:
Off (OFF)
[0]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter allows a choice of the function to be
activated if the value of the reference signal connected to
the input, terminal 1, falls below 50% of the setting in
parameter 336 for a period longer than the time set in
parameter 317.
If a time-out function (parameter 318) occurs at the same
time as a bus time-out function (parameter 514), the time-
out function (parameter 318) will be activated.
Settings:
No function
(NO OPERATION)
[0]
Ready signal
(UNIT READY)
[1]
Enable, no warning
(ENABLE/NO WARNING)
[2]
Running
(RUNNING)
[3]
Running, no warning
(RUNNING NO WARNING)
[4]
Running on reference, no warning
(RUNNING ON REFERENCE)
[5]
Fault
(FAULT)
[6]
Fault or warning
(FAULT OR WARNING)
[7]
Current limit
(CURRENT LIMIT)
[8]
Thermal warning
(THERMAL WARNING)
[9]
Reversing
(REVERSE)
[10]
Control word bit 11
(CONTROL WORD BIT 11)
[11]
Control word bit 12
(CONTROL WORD BIT 12)
[12]
Mechanical brake
(MECHANICAL BRAKE)
[20]
Sleep mode
(SLEEP MODE)
[21]
Table 3.9 323 Terminal X102, Relay Function (RELAY FUNC.)
The relay output can be used to give the present status or
a warning.
Relay
1 - 3 break, 1 - 2 make
Max. 250 V AC, 5 Amp.
Table 3.10
Description of choice:
Unit Ready signal
, the FC motor is ready for use.
Enable/no warning,
the FC motor is ready for use; no start
or stop command has been given (start/ disable). No
warning.
Running,
A start command has been given.
Running no warning,
A start command has been given. No
warning.
Running on reference,
no warning, speed according to
reference.
Fault,
output is activated by alarm.
Fault or warning
, the output is activated by alarm or
warning.
Current limit
, the current limit in parameter 221 has been
exceeded.
Thermal warning,
above the temperature limit in the
frequency converter.
Reverse
. Logic '1' = relay activated, 24 V DC on the output
when the direction of rotation of the motor is clockwise.
Logic '0' = relay not activated, no signal on the output,
when the direction of rotation of the motor is counter-
clockwise.
Control word bit 11
, if bit 11 = “1” in the control word
(both Fieldbus Profile and FC Profile) the relay will be
activated.
Control word bit 12
, if bit 12 = “1” in the control word
(both Fieldbus Profile and FC Profile) the relay will be
activated.
Mechanical brake
, enables control of an optional external
mechanical brake (see also parameter 138 and 139).
Sleep mode,
active when the unit is in sleep mode. See
.
327
Pulse reference/feedback, max. frequency
Value:
100-70000 Hz
[100-70000]
Programming
VLT
®
DriveMotor FCM Series
MG03BA02 - VLT
®
is a registered Danfoss trademark
47
3
3
Содержание VLT Brook Crompton Motor FCM 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Brook Crompton Motor FCM 300 www danfoss com drives...
Страница 2: ......
Страница 26: ...Illustration 2 5 Installation VLT DriveMotor FCM Series 24 MG03BA02 VLT is a registered Danfoss trademark 2 2...
Страница 37: ...Programming VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 35 3 3...
Страница 101: ...Index VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 99...
Страница 102: ...www danfoss com drives MG03BA02 175R0087 MG03BA02 Rev 2011 12 22...