Illustration 2.1 Key Diagram for FCM 300 Series
Terminal No.
Function
Example
1
Analogue input (0-20 mA)
Feedback signal
2
Analogue (0-10 V)/digital input 2
Speed reference
3
Digital input (or pulse) 3
Reset
4
Digital input (or precise stop) 4
Start
5
Digital input (other) 5
Jog (fixed speed)
6
24 V DC supply for digital inputs (max. 150 mA)
7
10 V DC supply for potentiometer (max. 15 mA)
8
0 V for terminals 1-7 and 9
9
Analogue (0-20 mA)/digital output
Fault indication
Table 2.2 X101: Terminal Block for Analogue/Digital Control Signals
-
Reset
to be closed short time for resetting fault trips
-
Start
to be closed for changing to
run mode
-
Jog
will run at fixed speed while closed (10 Hz)
-
Speed reference
(0-10 V) determines speed while in
run mode
Table 2.3 Connection Diagram - Factory Setting
Installation
VLT
®
DriveMotor FCM Series
14
MG03BA02 - VLT
®
is a registered Danfoss trademark
2
2