as the serial communication port can be used for switching
between Setups.
005
Programming Setup
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Active Setup (ACTIVE SETUP)
[5]
Function:
The choice is of the Set-up in which programming (change
of data) is to occur during operation. It is possible to
programme the two Set-ups independently of the Set-up
selected as the Active Set-up (selected in parameter 004).
Description of choice:
The
[0] Factory Setup
contains the factory data and can be
used as a data source if the other Set-ups are to be
returned to a known state.
[1] Setups 1
and
[2] 2
are individual Setups which can be
used as required. They can be programmed freely,
regardless of the Set-up selected as the Active Set-up and
thus controlling the functions of the FC motor.
006
Copying of Setups
Value:
No copying (NO COPY)
[0]
Copy to Setup 1 from # (COPY TO SETUP 1)
[1]
Copy to Setup 2 from # (COPY TO SETUP 2)
[2]
Copy to Setup all from # (COPY TO ALL)
[5]
# = the Setup selected in parameter 005
Function:
A copy is made from the Set-up selected in parameter 005
to one of the other Set-ups or to all the other Set-ups
simultaneously.
007
LCP copy
Value:
No copying (NO COPY)
[0]
Upload all parameters (UPLOAD ALL PARAM)
[1]
Download all parameters (DOWNLOAD ALL)
[2]
Download power-independent par.
(DOWNLOAD SIZE INDEP.)
[3]
Function:
Parameter 007 is used if it is desired to use the integrated
copying function of the control panel. You can therefore
easily copy parameter value(s) from one FC motor to
another.
Description of choice:
Select
[1] Upload all parameters
if all parameter values are
to be transmitted to the control panel. Select
[2] Download
all parameters
if all transmitted parameter values are to be
copied to the FC motor on which the control panel has
been mounted. Select
[3] Download power-independent par.
if only the power-independent parameters are to be
downloaded. This is used if downloading to a FC motor
that has a different rated power than the one from where
the parameter Set-up originates.
008
Display scaling of motor frequency
Value:
0.0-100.00
[1-10000]
1.00
[100]
Function:
This parameter chooses the factor to be multiplied by the
motor frequency, f
M
, for presentation in the display, when
parameters 009-012 have been set for Frequency x Scaling
[5].
Description of choice:
Set the desired scaling factor.
009
Display line 2
Value:
None
[0]
Reference [%] (REFERENCE [%])
[1]
Reference [unit] (REFERENCE [UNIT])
[2]
Feedback [unit] (FEEDBACK [UNIT])
[3]
Frequency [Hz] (FREQUENCY [Hz])
[4]
Frequency x Scaling [-] (FREQUENCY X SCALE)
[5]
Motor current [A] (MOTOR CURRENT [A])
[6]
Torque [%] (TORQUE [%])
[7]
Power [kW] (POWER [kW])
[8]
Power [HP] (POWER [hp] [US])
[9]
Motor voltage [V] (MOTOR VOLTAGE [V])
[11]
DC link voltage [V] (DC LINK VOLTAGE [V])
[12]
Thermal load, FC [%] (FC THERMAL [%])
[14]
Hours run [Hours] (RUNNING HOURS)
[15]
Digital input [Binary code] (DIGITAL INPUT [BIN])
[16]
External reference [%] (EXTERNAL REF [%])
[21]
Status word [Hex] (STATUS WORD [HEX])
[22]
Heat sink temp. [°C] (HEATSINK TEMP [°C])
[25]
Alarm word [Hex] (ALARM WORD [HEX])
[26]
Control word [Hex] (CONTROL WORD [HEX])
[27]
Warning word 1 [Hex]
(WARNING WORD 1 [HEX])
[28]
Warning word 2 [Hex]
(EXTENDED STATUS WORD [HEX])
[29]
Analog input 1 [mA] (ANALOG INPUT 1 [mA])
[30]
Analog input 2 [V] (ANALOG INPUT 2 [V])
[31]
Function:
This parameter allows a choice of the data value to be
displayed in line 2 of the display.
Parameters 010-012 enable the use of three additional data
values to be displayed in line 1.
For display read-outs, press the [DISPLAY/STATUS] button,
see
Programming
VLT
®
DriveMotor FCM Series
MG03BA02 - VLT
®
is a registered Danfoss trademark
37
3
3
Содержание VLT Brook Crompton Motor FCM 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Brook Crompton Motor FCM 300 www danfoss com drives...
Страница 2: ......
Страница 26: ...Illustration 2 5 Installation VLT DriveMotor FCM Series 24 MG03BA02 VLT is a registered Danfoss trademark 2 2...
Страница 37: ...Programming VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 35 3 3...
Страница 101: ...Index VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 99...
Страница 102: ...www danfoss com drives MG03BA02 175R0087 MG03BA02 Rev 2011 12 22...