Parameter
No.
Function
Range/number of settings/value
Factory setting
Data
type
Conv
.
index
200
Rotation direction
3
Only clockwise 0-132 Hz
5
0
201
Min. output frequency
(f
MIN
)
0.0 Hz-f
MAX
0.0 Hz
6
-1
202
Max. output frequency
(f
MAX
)
f
MIN
-f
RANGE
f
RANGE
(132 Hz)
6
-1
203
Reference/feedback
range
Min. - max./-max.- +max.
Min. - Max.
5
0
204
Minimum reference
-100,000.000-Ref
MAX
0.000
4
-3
205
Maximum reference
Ref
MIN
-100,000.000
50.000
4
-3
207
Ramp-up time 1
0.05-3600.00 s
3.00 s
7
-2
208
Ramp-down time 1
0.05-3600.00 s
3.00 s
7
-2
209
Ramp-up time 2
0.15-3600.00 s
3.00
7
-2
210
Ramp-down time 2
0.15-3600.00 s
3.00 s
7
-2
211
Jog ramp time
0.05-3600.00 s
3.00 s
7
-2
212
Quick stop ramp-down
time
0.05-3600.00 s
3.00 s
7
-2
213
Jog frequency
0 Hz - f
MAX
10.0 Hz
6
-1
214
Reference function
2
Sum
5
0
215
Preset reference 1
-100.00%-+100.00%
0.00%
3
-2
216
Preset reference 2
-100.00%-+100.00%
0.00%
3
-2
219
Catch up/slow down
value
0.00-100.00%
0.00%
6
-2
221
Current limit for motor
mode
Min.- max. limit in% of I
rated
Max. limit
6
-1
229
Frequency bypass,
bandwidth
0 (off)-100%
0%
6
0
230
Frequency bypass 1
0.0-132 Hz
0.0 Hz
6
-1
231
Frequency bypass 2
0.0-132 Hz
0.0 Hz
6
-1
241
Reference preset 1
-100.00%-+100.00%
0.00%
3
-2
242
Reference preset 2
-100.00%-+100.00%
0.00%
3
-2
243
Reference preset 3
-100.00%-+100.00%
0.00%
3
-2
244
Reference preset 4
-100.00%-+100.00%
0.00%
3
-2
245
Reference preset 5
-100.00%-+100.00%
0.00%
3
-2
246
Reference preset 6
-100.00%-+100.00%
0.00%
3
-2
247
Reference preset 7
-100.00%-+100.00%
0.00%
3
-2
Table 4.13 Functions to Programme, to Control and to Monitor via Bus (PROFIBUS) or by PC.
Parameter
No.
Function
Range/number of settings/value
Factory setting
Data
type
Conv.
index
317
Time out
1-99 s
10 s
5
0
318
Function after time out
Off/Stop and trip
Off
5
0
323
X102 relay function
14
No operation
5
0
327
Pulse reference/feedback, max. freq.
100-70000 Hz
5000 Hz
7
0
331
Terminal 1, analog input current
3
No operation
6
0
332
Terminal 2, digital input
31
Reference
6
0
333
Terminal 3, digital input
31
Reset
6
0
334
Terminal 4, digital input
30
Start
6
0
335
Terminal 5, digital input
29
Jog
6
0
336
Terminal 1, min. scaling
0.0-20.0 mA
0.0 mA
6
-4
337
Terminal 1, max. scaling
0.0-20.0 mA
20.0 mA
6
-4
338
Terminal 2, min. scaling
0.0-10.0 V
0.0 V
6
-1
339
Terminal 2, max. scaling
0.0-10.0 V
10.0 V
6
-1
340
Output functions
24
No operation
6
0
Table 4.14 Functions to Programme, to Control and to Monitor via Bus (PROFIBUS) or by PC.
All about FCM 300
VLT
®
DriveMotor FCM Series
MG03BA02 - VLT
®
is a registered Danfoss trademark
91
4
4
Содержание VLT Brook Crompton Motor FCM 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Brook Crompton Motor FCM 300 www danfoss com drives...
Страница 2: ......
Страница 26: ...Illustration 2 5 Installation VLT DriveMotor FCM Series 24 MG03BA02 VLT is a registered Danfoss trademark 2 2...
Страница 37: ...Programming VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 35 3 3...
Страница 101: ...Index VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 99...
Страница 102: ...www danfoss com drives MG03BA02 175R0087 MG03BA02 Rev 2011 12 22...